Codes d'erreurs
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

MUEN-HG
SERIES:
UNITS:
MUEN-30-HG
No
Code
1
E0
Water flow detection error (The third time)
2
E1
Power phase sequence error
3
E2
Communication error
4
E3
Total water outlet temperature sensor error
5
E4
Outlet water temperature sensor error in shell and tube exchanger
6
E5
Pipe temperature sensor error in condenser A
7
E6
Pipe temperature sensor error in condenser B
8
E7
Outdoor ambient temperature sensor error
9
E8
Air discharge temperature sensor error in digital compressor in system A
10
E9
Water flow detection error (The first and second times)
11
EA
Main unit detected
12
EB
Anti-freezing
13
EC
Wired controller did not find out any on-line module unit
14
ED
Wired controller and module unit communication error
15
Ed
1-hour consecutive 4-times PE protection
16
EE
Wired controller and computer communication error
17
EF
Inlet water temperature sensor error
18
P0
High pressure or air discharge temperature protection in system A
19
P1
Low pressure protection in system A
20
P2
High pressure or air discharge temperature protection in system B
21
P3
Low pressure protection in system B
22
P4
Current protection in system A
23
P5
Current protection in system B
24
P6
Condenser high pressure protection in system A
25
P7
Condenser high pressure protection in system B
26
P8
Air discharge temperature sensor protection in digital compressor in system A
27
Pb
System
28
PE
Low-temperature protection of double-pipe heat exchanger
29
F1
EEPROM failure
30
F2
Failure of reduction of wired controller number at parallel connection of multiple wired controller (reserved)
MUEN-H6
(CL25601 to CL25605)
(CL25604)
temperature sensor 1 error in shell and tube exchanger
anti-freezing
protection
TROUBLESHOOTING
(CL25616 to CL25617)
Trouble