mundoclima 2022 Manuel page 100

Codes d'erreurs
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

MUENR-H4
SERIES:
MUENR-H6
UNITS:
MUENR-05-H4
MUENR-07-H4
MUENR-05-H6
MUENR-07-H6
E9
EEPROM malfunction
H0
Communication malfunction between main chip and IPDU.
E4
T3,T4 sensor malfunction
E5
Voltage protection malfunction
E6
DC fan motor malfunction
EA
A fan in the A region run for more than 5 minutes in heating mode
Eb
There are two times E6 fault in 10 minutes (recovery after power off)
HH
Inlet water temperature sensor malfunction for 5/7kW models.
EC
Outlet water temperature sensor malfunction (5/7kW)
C0
Temperature sensor malfunction of plate heat exchanger for 5/7kW.
P1
High pressure protection
P2
Low pressure protection
P3
Current protection of the compressor
P4
Discharged temperature protection
P5
T3 high temperature protection of outdoor condenser
P6
IPDU module protection
P8
Typhoon protection
Protection when temperature difference between inlet & outlet water in heating mode is too
CH
large for 5/7kW
Protection when temperature difference between inlet & outlet water in cooling mode is too
CL
large for 5/7kW.
CP
Anti-freeze protection of plate heat exchanger for 5/7kW
Pb
System anti-freeze protection
C8
Water flow switch protection malfunction
PH
Protection when water temperature in heating mode is too high for 5/7kW.
dF
Defrosting
d8
Remote contact ON / OFF is active
Wired controller error code list KJR-120F1/BMK-E (CL92340):
EEPROM error code(Wire controller)
EEPROM malfunction
5-minute error for heating mode fan
in area A
Two times of E6 protection in 10 minutes
T3&T4 temperature sensor malfunction
Voltage protection
DC fan motor malfunction
Communication malfunction between
the main controlling chip and IPDU
(CL25610 to CL25615)
(CL25620 to CL25628)
(CL25610)
(CL25611)
(CL25620)
(CL25621)
Tin temperature sensor malfunction
Tout temperature sensor malfunction
Flow switch malfunction
High temperature protection in heating mode
Low temperature protection
in heating mode
Anti-idling protection of water pump
Tb1 temperature sensor malfunction
Tb2 temperature sensor malfunction
TROUBLESHOOTING
High pressure protection
Low pressure protection
Outdoor units current protection
Compressor discharge temp. Protection
Condenser high temperature protection
IPM mode protection
Typhoon protection
100
EN
Note
The same as
10-16kW
5/7kW
The same as
10-16kW
5/7kW
The
same
as 10-16kW
5/7kW
The same as
10-16kW
Outdoor units anti-freezing protection
Radiator high temperature protection
Water inlet and outlet temp. difference too
large protection
Communication error beetwen the wired
E2
controller and the chiller unit.

Publicité

Table des Matières
loading

Table des Matières