BATTERY REPLACMENT PROCEDURE:
1
1. Remove the front panel.
3
3. Then remove the cover.
5
5. Remove the three retaining screws.
REMINDER! The used batteries are hazardous wastes and must be disposed through recycling. Most retailers
that sell lead-acid batteries collect used batteries for recycling, as required by the local regulations.
Copyright © 2016 CyberPower Systems, Inc.
BATTERY REPLACEMEN (continued)
2
2. Remove the retaining screw of the cable
protection cover.
4
4. Disconnect the black wire and red wire
from the battery.
6
6. Replace the new battery pack back into
the compartment. Tighten up the screws
and replace the cable protection cover
and the front panel. Recharge the unit for
12 hours to ensure the UPS performs
expected runtime.