7.8.5.5 Submenu for Preset 1
Submenu Preset 1
Preset 1 ON/OFF
Preset 1 ON
Preset 1 OFF and no function
Output signal
ADD mode output operations:
permanent signal at Output 1,
becomes active when count >
Preset 1
SUB mode output operations:
S
permanent signal at Output 1,
becomes active when count <
Preset 1
A
ADD mode output operations:
permanent signal at Output 1,
becomes passive when count >
Preset 1
SUB mode output operations:
permanent signal at Output 1,
becomes passive when count <
Preset 1
ADD mode output operations:
timed signal at Output 1,
becomes active when count >
Preset 1 (activation only in
positive direction).
SUB mode output operations:
timed output at Output 1,
becomes active when count <
Preset 1 (activation only in
negative direction).
ADD mode output operations:
timed signal at Output 1,
becomes passive when count >
Preset 1 (deactivation only in
positive direction).
SUB mode output operations:
timed output at Output 1,
becomes passive when count <
Preset 1 (deactivation only in
negative direction).
ADD mode output operations:
timed signal at Output1,
becomes active with positive
direction and when count >
Preset 1 and subsequently active
with negative direction and when
count < Preset 1
SUB mode output operations:
timed signal at Output 1,
becomes active with negative
direction and when count <
Preset 1 and subsequently active
Page 14
with positive direction and when
count > Preset 1
A
ADD mode output operations:
timed signal at Output1,
becomes passive with positive
direction and when count >
Preset 1 and subsequently
passive with negative direction
and when count < Preset 1
SUB mode output operations:
timed output at Output 1,
becomes passive with negative
direction and when count <
Preset 1 and subsequently
passive with positive direction
and when count > Preset 1
Duration of timed signal of
Output 1
programmable from 00.01 to
99.99 sec.
Timed signal is post-triggered
7.8.5.6 Submenu for Preset 2
Output signal
ADD mode output operations:
permanent signal at Output 2,
becomes active when count >
Preset 2
SUB mode output operations:
S
permanent signal at Output 2,
becomes active when count <
zero
ADD mode output operations:
permanent signal at Output 2,
becomes passive when count >
Preset 2
S
SUB mode output operations:
permanent signal at Output 2,
becomes passive when count <
zero
ADD mode output operations:
timed signal at Output 2,
becomes active when count >
Preset 2 (activation only in
positive direction).
SUB mode output operations:
timed signal at Output 2,
becomes active when count <
zero (activation only in negative
direction).
ADD mode output operations:
timed signal at Output 2,
becomes passive when count >
Preset 2 (deactivation only in
positive direction).
SUB mode output operations:
timed signal at Output 2,