The quality of the insulation is a function of the results found.
DAR
< 1.25
< 1.6
> 1.6
3.4. ADjUSTMENT OF THE vARIABLE TEST vOLTAGE
This function makes it possible to use test voltages other than the 4 available.
Set the switch to SET Var.
SET Var
SET Var
OFF
Change it using the
and
This value is retained in a non-volatile memory.
PI
Condition of the insulation
< 1
Inadequate or even
< 2
< 4
> 4
The test voltage flashes.
Then set the switch to Var 50 - 5000 V to make
keys.
the measurement.
V
dangerous
Good
Excellent
V
Var
Var
50-5000V
50-5000V
OFF