BTL7-A/C/E/G5 _ _ -M _ _ _ _ -HB/WB-KA_ _/K_ _/FA_ _/F_ _
Micropulse Transducer - Rod Style
4
Installation and connection (continued)
4.5
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
–
Connect transducer and controller using a shielded
cable.
Shielding: Braided copper shield with minimum 85%
coverage.
–
On the transducer side, the cable shielding is
connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system.
It is important to maintain adequate distance between the
transducer/holding cylinder and strong, external magnetic
fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-A/G
Max. 30 m
BTL7-C/E
Max. 100 m
Prerequisite: Construction, shielding and routing preclude the effect of any
1)
external noise fields.
Tab. 4-3:
Cable lengths BTL7