English
4.6 COMPLIANCE WITH INTERNATIONAL
STANDARDS
Electrical safety :
Electromagnetic
compatibility :
Mechanical
strength :
Degree of protection
of the housing :

4.7 VARIATIONS IN DOMAIN OF USE

Quantity of influence Range of influence
Temperature
Frequency
55 - 139
Application of safety rules as per standard
EN-61010-1.
1000V CAT-III - 600V CAT-IV.
Pollution level 2. Double insulation.
Compliant with standard EN-61326-1
Residential environment
Free fall: 1m (in accordance with standard
IEC-68-2-32)
IP54 as per EN 60529
0°C to + 50°C
1 to 3 kHz
Influence
V AC : 0.5%L/10°C
mV DC : 0.5%L/10°C
Ω (R>20 MΩ) :
0.5%L/10°C
µF (C>50 µF) :
5%L/10°C
V AC : 10%L + 1ct