1.
General instructions
Warning! Analogue signal isolators from the WAVE
must be installed by qualified personnel only. Auxiliary power
should only be supplied after the device has been
installed correctly. It is not permitted to undertake changing the
range when in operation, because parts that are dangerous to
touch are unprotected. A screwdriver, correctly insulated against
the input voltage, must be used when making fine adjustments
via the potentiometers at the front of the module.
National regulations (for example, DIN VDE 0100 in Germany)
must be observed when selecting and installing supply cables.
Protective measures must be taken against electrostatic
discharges (ESD) when mounting and setting WAVE
devices.
2.
Application
Analogue signal isolators are used for galvanic isolation and conversion of
temperature, resistance and potentiometer signals. Input and output
signals are calibrated switch selectable via DIP switches. It is not
necessary to adjust the pre-settable measurement ranges. A +/- 12.5 %
variation can be achieved in the respective range by switching in
potentiometers for zero and span. The analogue signal is linear to the
temperature and to the resistance or to the potentiometer setting.