20
UK
10 - DIP SWITCH DIP2
The settings are stored during the rest phase (gate closed).
The default settings are highlighted in the boxes with grey background.
DIP
Function
FUNCTIONING
changing this setting will
2_4
reset the control board and
a new learning cycle will be
required.
ANTI
2_5
CRUSHING
SPIA
/
2_6
FLASHING LIGHT
FUNCTIONING
2_7
TERMINAL 18
FINAL STROKE
2_8
IN CLOSING
DECELERATION
DISTANCE
changing this setting will
2_9
reset the control board and
a new learning cycle will be
required.
2_10
UNUSED
Status
ON
ENCODER
TIME
OFF
Anti crushing active.
-It is not active in the proximity of mechanical end stops.
-After anti crushing intervention the gate will reverse its movement for 1s, after a short
ON
pause the movement will continue at slow speed.
-Subsequently to 3 consecutive anti crushing interventions the control board will
STOP and a user command will be required to start again the motion.
-Anti crushing is not active when working by time ( DIP2_4 = OFF)
Anti crushing disabled.
OFF
Terminal M2_7 and M2_8 work as WARNING LIGHT.
ON
Terminal M2_7 and M2_8 work as FLASHING LIGHT.
OFF
Terminal 18 works as START input, but it will not make the automatic closing even
ON
if enabled.
Terminal 18 works as PEDESTRIAN input.
The pedestrian manoeuvre is made with condominium logic on leaf 1 and is not
OFF
modifiable. The automatic closing is active if the automatic general closing is active.
Enables the final stroke in closing function
Operation:
After slowing down, the movement continues in slow down mode for 1s to facilitate
ON
the locking of the electric lock.
During the final stroke in closing the safety devices and the commands are not
active (PHOTO, EDGE, START, etc.)
Disables the final stroke in closing function
OFF
Long deceleration (~33% of the total stroke).
ON
Irrelevant if DIP2_4=OFF.
Short deceleration (~25% of the total stroke).
OFF
Description
BE24