Technical Data - Honeywell DTI Serie Fiche Technique Et Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

GENERAL
The DTI 2-Wire Differential Pressure Transmitters with
current signal output are suitable for measuring differential
pressures in liquid and gaseous media. They operate
according to the piezo-resistive measuring principle. The
measurement cell is welded into a seal-less stainless steel
measurement chamber. The device is powered with
10...30 VDC and has a 4...20 mA output. Typical areas of
application include:
Compressors
Refrigeration and HVAC/R
FEATURES
Compact, rugged design
Accurate differential pressure measurement over a wide
temperature range
Rated IP65
Rapid response time
2-wire technology

TECHNICAL DATA

Connection
Pressure connection
2X G1/8" as per DIN ISO 228
Elect. connection
Plug connector as per DIN 175301, Form
A, wire cross-section max. 1.5 mm
Sensor
(Reference conditions: As per DIN 16086 + DIN EN 60770)
Medium temperature
-15 ... +100 °C
Operating temperature
-20 ... +80 °C
Storage temperature
-50 ... +100 °C
measuring
max. system
Model
range
pressure
DTI06
0 ... +0.6 bar
DTI1
0 ... +1 bar
DTI2
0 ... +2.5 bar
DTI4
0 ... +4 bar
DTI6
0 ... +6 bar
DTI10
0 ... +10 bar
1)
Max. ambient temperature +60 °C
3)
Incl. linearity, hysteresis, reproducibility, and temperature drift in the range of -15 ... +85 °C
® U.S. Registered Trademark
Copyright © 2019 Honeywell Inc. • All rights reserved
2-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS
2
Table 1. Measuring ranges, max. permissible loads, etc.
max. load
both sides
2)
+ side
5 bar
7.5 bar
7.5 bar
10 bar
15 bar
15 bar
30 bar
1)
45 bar
25 bar
30 bar
2)
With simultaneous application of the pressure on the + and – side
PRODUCT DATA AND MOUNTING INSTRUCTIONS
Zero-point deviation
≤ 0.3% of FFS
Thermal hysteresis
-15 ... +85 °C in compensated range
Char. curve deviation
≤ ±0.5% of FFS
Hysteresis
≤ ±0.2% of FFS
Reproduceability
≤ 0.1% of FFS
Response time
< 3 ms
Long-term stability
< 1% of measurement range / year
Effect of ambient temperature in compensated range
of -20 °C ... +85 °C
Zero
≤ 0.02% / K (typically),
≤ 0.04% / K max.
Measuring range
≤ 0.02% / K (typically),
≤ 0.04% / K max.
Output
Output signal
4...20 mA
Burden
≤ (U
B
Voltage supply
10...30 VDC
Current consumption
max. 25 mA
Effect of voltage supply
< 0.02% / V
Materials
In contact with medium
stainless steel 1.4571, 1.4435, 1.4305;
seal: FPM
Miscellaneous
EMC
According to EN 61326
Protection rating
IP65 as per EN 60529 with plug con-
nector as per DIN 175301, Form A
Mechanical shock
Max. 100 g / 1 ms (as per DIN IEC 68-2-
27)
Mechanical vibrations
Max. 20 g at 15...2000 Hz (as per DIN
IEC 68-2-6)
Mounting orientation
As desired
Weight
100 g
Incl. in delivery
Pressure transmitter, incl. plug connector
and these instructions in individual
packaging
China RoHS Conformity
See accompanying leaflet
DTI6
0-6bar, 24VAC/DC, 0-10V, IP65
Honeywell GmbH, Böblingerstr. 17
71101 Schönaich, Made in Germany
Fig. 1. Manufacturer's plate (example)
bursting
total error
pressure
- side
5 bar
≥ 60 bar
10 bar
40105000T94Z001K001 – TN:00695088
DTI Series
– 10 V) / 0,02 A
20
1645
XXX-XXXXX
long-term
3)
(FFS)
stability (p.a.)
≤ 2.3%
≤ 0.6%
≤ 2.0%
≤ 0.6%
≤ 1.8%
≤ 0.4%
≤ 1.5%
MU0B-0770GE51 R0619