6 - CONFIGURING THE UNIT
6.2 - Humidifier parameters (visible if P10 =2)
6.2.1 - Settings (sub-menu 9.1)
Access level
No.
Description
3
900
Maximum production
3
901
Off delay time
Water conductivity
3
902
(0 = automatic measurement > 0 =
forced conductivity)
3
903
Conductivity pre-alarm threshold
3
904
Conductivity alarm threshold
Foam detection threshold control
(0 = foam detection excluded
3
905
1 = max. foam detection sensitivity;
100 = min. foam detection sensitivity)
Internal conductivity control of the
cylinder on warm-up as compared to
3
906
the nominal (less than 100%:
conductivity increases)
Control of the duration of release for
3
907
dilution
Cylinder maintenance limit time (0 =
"CY" cylinder life and maintenance
3
908
alarm no longer appears as a matter
of course)
Limit time between two periodic
3
909
releases
3
910
Days of inactivity awaiting release
2
911
Manual drain
2
912
Prewashing
6.2.2 - Reading parameters (sub-menu 9.2)
Access level
No.
1
950
Outdoor request display
1
951
Display of the instantaneous steam flow rate (instantaneous steam)
1
952
Conductivity of supply water
1
953
Current consumed
Maximum production display
1
954
(corresponding to the configured P900 value)
1
955
Nominal steam production
Cylinder hours counter
1
956
(can be reset to 0 by pressing the reset+0 keys for 5 secs)
Machine hours counter
1
957
(cannot be reset to zero; read only)
Humidifier state
0: Not activated
1: Evaporation cycle start
2: Charging with water
3: Evaporating
4: AFS drain
1
958
5: Water drain (for dilution or manual)
6: Water drain ended
7: Complete drain for extended period of inactivity
8: Network or manually requested complete drain
9: Water shortage management
10: Prewash
11: Periodic drain
60
Setting
20 to 100%
0 s to 120 s
0 to 125 µS/cm
0 to 2000 µS/cm
0 to 2000 µS/cm
0 to 100%
50 to 200%
50 to 200%
0 h to 4000 h
1 h to 240 h
1 to 199 days
0: without
1: with
0: without
1: with
Description
By default Display condition
100%
P10 = 2
0 s
P10 = 2
0 µS/cm
P10 = 2
1500 µS/cm P10 = 2
2000 µS/cm P10 = 2
50 %
P10 = 2
100%
P10 = 2
100%
P10 = 2
3000 h
P10 = 2
24 h
P10 = 2
3 days
P10 = 2
P10 = 2
P10 = 2
Unit
Display condition
%
P10 = 2
kg/h
P10 = 2
µS/cm
P10 = 2
A
P10 = 2
kg/h
P10 = 2
kg/h
P10 = 2
h
P10 = 2
h
P10 = 2
P10 = 2