Max. output power (+140 °F)
Rated apparent power
Phases
Nominal grid voltage
Operating range AC voltage
Adjustment range for grid voltage
Max. continuous output current at V
Recommended min. AC overcurrent protection
Max. output fault current per duration
Nominal frequency
Total harmonic distortion
Power factor (cos phi)
General data
Maximum efficiency
CEC efficiency
Cooling
Protection class
Dimensions h x w x d
Weight (full/lite version)
Permitted ambient temperature
Permitted storage temperature
Permissible humidity
Noise emission
Protection devices
Reverse polarity protection
Stand-alone operation protection
Arc Fault Circuit Interrupter/interruption
Photovoltaic insulation monitoring
High temperature
at 440 V
at 480 V
at 440 V
at 480 V
at 440 V
nom
at 480 V
at 440 V
at 480 V
at 440 V
at 480 V
15.0-3 480
12,200 W
14,400 W
14,995 VA
3 ~ NPE
254 V / 440 V
277 V / 480 V
-12 to +10%
127–322 V/220–558 V
19.7 A
18.0 A
25.0 A
25.0 A
30.9 A / 150.4 ms
50/60 Hz
< 1.5%
0 - 1 ind./cap.
98.00%
97.00%
Controlled forced-air ventilation
NEMA 4X
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
95.7/95.0 lbs. (43.4/43.1 kg)
-40 °F to +140 °F (-40 °C to +60 °C)
-40 °F to +158 °F (-40 °C to +70 °C)
0 - 100%
65 dB(A) (ref. 1pW)
Integrated
Integrated
Integrated
Integrated
Operating point shift/
active cooling
3)