TH2250 A
POMPE D'EVACUATION DES CONDENSATS
Tension nominale
Nominal voltage
Puissance absorbée
Power input
Intensité absorbée
Intensity input
Voir spécifications de montage détaillées dans la notice d'installation fournie avec le matériel.
See mounting specifications in the installation instructions supplied with the material.
EVACUATION DES CONDENSATS - CONDENSATE DRAINING
Hose connection
Condensate drain pipe heat insulated
CONDENSATE PUMP
SPECIFICATIONS POMPE - PUMP SPECIFICATIONS
Débits d'eau max. = 240 l/h
Waterflow max. = 240 l/h
Hauteur max. de refoulement = 0,5 mCE
Max. height of discharge = 0.5 mCE
INSTALLATION - MONTAGE
Système d'évacuation
Drain system
MODELES FROID SEUL-REVERSIBLES
COOLING ONLY-HEATPUMP MODELS
The smallzised condensate pump is built into the air
treatment unit. It has been especially designed to
remove condensates from the the upper part to improve
draining. Provide for draining by gravity with a slope
and a siphon outside of the appliance, according to
the rule book.
1 ~ 230 V - 50 Hz
16 W
0,12 A
The Air Treatment Unit is equipped with a pump to lift
condensates to the top level of the unit.
Provisions should be made according to the rule book,
to drain by gravity with slope and odor trap outside of
the appliance.
1 : 100 slope
Système d'évacuation avec plusieurs caissons
Drain system with several units
Odor trap