CLIMATISEURS INDIVIDUELS
ROOM AIR CONDITIONERS
96TKF04G TECHNICAL DATA
"CASSETTE" COLORADO
Froid seul - Cooling only
Réversible - Heatpump
K 30F•45FA

Publicité

Table des Matières
loading

Sommaire des Matières pour Airwell K 30F

  • Page 1 CLIMATISEURS INDIVIDUELS ROOM AIR CONDITIONERS "CASSETTE" COLORADO Froid seul - Cooling only Réversible - Heatpump K 30F•45FA 96TKF04G TECHNICAL DATA...
  • Page 2 SOMMAIRE SUMMURY PRESENTATION DESCRIPTION SPECIFICATIONS TECHNIQUES TECHNICAL SPECIFICATIONS PERFORMANCES FRIGORIFIQUES COOLING PERFORMANCE ZONE D'EXPLOITATION WORKING RANGE ENCOMBREMENTS DIMENSIONS INSTALLATION MONTAGE POMPE D'EVACUATION DES CONDENSATS CONDENSATE PUMP EMETTEUR DE TELECOMMANDE - RC4 RC4 - INFRARED REMOTE CONTROL EMITTER CHAUFFAGE ELECTRIQUE ELECTRIC HEATING LIAISONS FRIGORIFIQUES COOLING PIPES FILTRATION...
  • Page 3: Présentation

    CLIMATISEURS "SPLIT-SYSTEM CASSETTE" "SPLIT-SYSTEM CASSETTE" AIR CONDITIONERS PRÉSENTATION DESCRIPTION This range of "CASSETTE" type aircooled air CASSETTE conditioners offers the utmost of confort at low installa- tion costs. These units are suitable for decentralized installations of any capacity. They require only a small floorspace; the attractively looking cassette fits perfectly into standard modules of a false ceiling.
  • Page 4: Liaisons Frigorifiques

    3. LIAISONS FRIGORIFIQUES 3 - COOLING LINKING PIPES The two indoor and outdoor units are equipped with flare couplings allowing to use flare cooling pipes (copper pipes of cooling quality equipped at their ends with nuts). 4. DESCRIPTION 4 - DESCRIPTION 4.1 Habillage 4.1.
  • Page 5: Chauffage Thermodynamique

    4.6. Chauffage électrique 4.6. Electric heating - The Cassettes are factory-equipped with electric heating to be connected on site. - The electric heating equipped with heating resistances is heat protected against any abnormal raise of temperature by two thermostats : •...
  • Page 6 MODELES FROID SEUL-REVERSIBLES TH2240 C COOLING ONLY-HEATPUMP MODELS SPECIFICATIONS TECHNIQUES TECHNICAL SPECIFICATIONS Modèles K 30F K 45FA MODELS • Nominal cooling capacity (1) • Nominal supply voltage 230 V/50 Hz • Air flow (average values) Treated air Fresh air • Nominal power supply...
  • Page 7: Performances Frigorifiques Cooling Performance

    TH2241 B MODELES FROID SEUL-REVERSIBLES COOLING ONLY-HEATPUMP MODELS PERFORMANCES FRIGORIFIQUES COOLING PERFORMANCE Pt (W) Modèle / Model K 30F Total cooling capacity Latent cooling capacity ensible cooling capacity Outdoor dry bulb Indoor dry bulb Indoor wet bulb Indoor relative hygrometry...
  • Page 8: Zone D'exploitation Working Range

    AIR A TRAITER AIR TO BE TRAITED REGIME CONTINU - DEBIT D'AIR NOMINAL CONTINUOUS RUNNING - NOMINAL AIR FLOW CONDITIONS DE FONCTIONNEMENT WORKING MODE Modéles / Models K 30F K 45FA LIMITES INFERIEURES Indoor temperature MINIMUM TEMPERATURE MINIMUM Outdoor temperature...
  • Page 9 TH2244 C MODELES FROID SEUL-REVERSIBLES COOLING ONLY-HEATPUMP MODELS ENCOMBREMENTS DIMENSIONS CAISSON DE TRAITEMENT - AIR TREATMENT UNIT K 30 F / K 45 FA × 4 oblongs holes 10 × 30 DESCRIPTION False ceiling T-shaped rod (false ceiling) Evaporator Succion grille Electric box (removable) Draining of condensates "GAS"...
  • Page 10: Degagements A Prevoir A L'installation

    MODELES FROID SEUL-REVERSIBLES TH2246 C COOLING ONLY-HEATPUMP MODELS ENCOMBREMENTS DIMENSIONS GROUPE DE CONDENSATION - CONDENSING UNIT GC 30 F FACE AVANT - FRONT PANEL Dimensions in mm Access electric terminal strip Discharge grille Flare couplings Æ 10 x 13 4 trous oblongs Æ...
  • Page 11 TH2247 C MODELES FROID SEUL-REVERSIBLES COOLING ONLY-HEATPUMP MODELS ENCOMBREMENTS DIMENSIONS GROUPE DE CONDENSATION - CONDENSING UNIT GC 45 FA Dimensions in mm Power supply cable inlet throught the side panel. Pressure tapes DEGAGEMENTS A PREVOIR A PROVIDE FOR FOLLOWING L'INSTALLATION INSTALLATION CLEARANCES (Cotes minimales) (Minimum dimensions)
  • Page 12: Installation/Montage

    MODELES FROID SEUL-REVERSIBLES TH2248 B COOLING ONLY-HEATPUMP MODELS INSTALLATION MONTAGE Voir spécifications de montage détaillées dans la notice d'installation fournie avec le matériel. See mounting specifications in the installation instructions supplied with the material. GROUPE INTERIEUR INDOOR UNIT The Air Treatment Units fits into a false ceiling of stan- dard 600 x 600 mm modules.
  • Page 13: Diffusion De L'air Traite

    DIFFUSION DE L'AIR TRAITE DISTRIBUTION OF TREATED AIR Place the Air Treatment Unit in the center of the room to allow air to be distributed on all four faces of the appliance. it is possible to close the discharge on 1 or 2 faces in order to adapt the air distribution to the constraints of the room to be treated (see figure here under).
  • Page 14: Renouvellement D'air Neuf Fresh Air Intake

    RENOUVELLEMENT D'AIR NEUF FRESH AIR INTAKE Fresh air flow should not exceed 20% of nominal air flow. Modèles / Models K 30F K 45FA Nominal air flow (high speed) Maximal fresh air flow Soufflage d'air traité dans un local adjacent...
  • Page 15: Pompe D'evacuation Des Condensats Condensate Pump

    TH2250 A MODELES FROID SEUL-REVERSIBLES COOLING ONLY-HEATPUMP MODELS POMPE D'EVACUATION DES CONDENSATS CONDENSATE PUMP The smallzised condensate pump is built into the air treatment unit. It has been especially designed to remove condensates from the the upper part to improve draining.
  • Page 16: Émetteur De Télécommande Infrared Remote Control Emitter

    MODELES FROID SEUL-REVERSIBLES TH2251 B COOLING ONLY-HEATPUMP MODELS ÉMETTEUR DE TÉLÉCOMMANDE INFRARED REMOTE CONTROL EMITTER ON/OFF key COOL, HEAT, AUTO HEAT/COOL, FAN, DRY mode selector I FEEL key: local detection of the temperature FAN SPEED/AUTO FAN selector Key to raise the room temperature Key to lower the room temperature SLEEP Key Auto swing...
  • Page 17: Chauffage Electrique Electric Heating

    TH2252 C MODELES FROID SEUL-REVERSIBLES COOLING ONLY-HEATPUMP MODELS CHAUFFAGE ELECTRIQUE ELECTRIC HEATING The electric heating of the cassettes is composed of heating resistances placed inside the pipes of the evaporator. These resistances are heat protected against any abnormal temperature rise by two ther- mostats equipped with a "positive safety"...
  • Page 18 GC 30F / RCF is installed above the processing unit (interconnecting tubes with a bottle). Modèles / Models H. maxi. (m) K 30F K 45FA * sans siphon / whitout siphon...
  • Page 19 (see installation instructions). Diamètre de tubes de liaison : Diameter of the linking pipes : Models K 30F K 45FA Characteristics Pipe Ø GAS PIPE Pipe Ø...
  • Page 20 MODELES FROID SEUL-REVERSIBLES TH2254 A COOLING ONLY-HEATPUMP MODELS FILTRATION FILTER - Filter type: Rapidly removable cassettes - Type de filtre : Cassettes à dépose rapide - Type média : Tissé synthétique - Media: Woven synthetics - Classement au feu : M4 (PV LNE N° 812 02 29 - Fire resistance: M4 (PV LNE No 812 02 29 du 30/01/89)
  • Page 21: Raccordements Electriques

    TH2255 B MODELES FROID SEUL-REVERSIBLES COOLING ONLY-HEATPUMP MODELS RACCORDEMENTS CONNECTIONS The cooling and electric connections to be made between the two units are explained in detail in the installation instructions supplied with the appliance. ORIFICES DE RACCORDEMENT PORTS FOR CONNECTION CAISSON DE TRAITEMENT (ST) - AIR TREATMENT UNIT (ST) : Flare valves located on the side of the appliance.
  • Page 22 MODELES FROID SEUL TH2256 C COOLING ONLY MODELS SPECIFICATIONS ELECTRIQUES POUR L'INSTALLATION ELECTRICAL SPECIFICATIONS FOR INSTALLATION TYPE D'APPAREIL K 30 F TYPE OF APPLIANCE Power supply 1 ~ 230 V - 50 Hz FROID + VENTILATION COOLING + VENTILATION Nominal current Maximum current Fuse rating aM Fuse rating ASE/VDE*...
  • Page 23: Raccordement Electriques Electrical Connections

    TH2257 E MODELES FROID SEUL COOLING ONLY MODELS RACCORDEMENT ELECTRIQUES ELECTRICAL CONNECTIONS Alimentation 1 N ~ 230 V Power supply 1 N ~ 230 V K 30 F GC 30 F Fil de sonde venant de K Sensor wire coming from the K 1 N ~ 230 V Alimentation 3 N ~ 400 V Power supply 3 N ~ 400 V...
  • Page 24 MODELE REVERSIBLE HEAT PUMP MODEL This chapter includes specifications relative to the heatpump model : heating performance, and electrical connections. All characteristics common with the standard model : - cooling performance, - filtration, - heating, - dimensions, - principles of connection, ... are explained on the plates of the technical instruc- tions, which the 2 types of appliance have in common.
  • Page 25: Chauffage Electrique

    The 2 algorhythms adjust the time between 2 defrosting cycles in order to optimise the performance of the air conditioning unit. The algorhythm will automatically increase the time between 2 defrosting cycles and reduce the cycles, depending on requirements. For appliances equipped with electric heating : The electric heating in the heatpump systems is forced for heating and ventilation, and the treatment unit will operate at low speed in relation to the evaporator...
  • Page 26: Performances Calorifiques Heating Capacity

    * L'accessoire chauffage électrique est indispensable pour fonctionnement par température extérieure négative (< 0 °C). * The electric heating accessory is necessary for operation at negative outdoor temperatures (- 0 °C). Modèle / Model K 30F = Puissance calorifique totale = Total heating capacity Tse = Outdoor dry bulb Tse = Température sèche extérieure...
  • Page 27 TH2260 C MODELES REVERSIBLES HEATPUMP MODELS SPECIFICATIONS ELECTRIQUES POUR L'INSTALLATION ELECTRICAL SPECIFICATIONS FOR INSTALLATION TYPE D'APPAREIL K 30 F K 45 FA TYPE OF APPLIANCE Power supply 3 N ~ 400 V - 50 Hz FROID + VENTILATION (OU CHAUFFAGE COOLING + VENTILATION (OR HEATPUMP THERMODYNAMIQUE) HEATING)
  • Page 28: Raccordements Electriques Electrical Connections

    MODELES REVERSIBLES TH2261 C HEATPUMP MODELS RACCORDEMENTS ELECTRIQUES ELECTRICAL CONNECTIONS K 45 FA K 30 F GC 30 RCF GC 45 RCFA Fil de sonde venant de K Fil de sonde venant de K Sensor wire coming from the K Sensor wire coming from the K 3 N ~ 400 V Borne(s) existante(s) dans les cas avec chauffage électrique.
  • Page 30 FRANCE : 1 bis,Avenue du 8 Mai 1945 Saint-Quentin-en-Yvelines 78284 GUYANCOURT Cedex Fax 33 1 39 44 11 55 Tél. 33 1 39 44 78 00 www.airwell.com ACE Klimatechnik GmbH DEUTSCHLAND : Berner Straße 43 www.airwell.de Tel. 0 69/507 02-0...