Please carefully read these notes before projecting. The files with the suffix .200 can be found in the
folder TypDat.
Standard and extended formats
There are GSD files, whose module is transmitted using an extended ident. no.
(e.g. 0x42, 0x84, 0x08, 0x05). These GSD files can be found in the folder Extended. Furthermore
the GSD files with a standard ident. (e.g. 0x94) can be found in the folder Standard. When integra-
ting field transmitters the GSD files with an extended ident. should always be used first. If the inte-
gration fails, then the standard GSD should be used. This difference is the result of a specific imple-
mentation in the Master system.
Contents of the download file from the Internet and the CD-ROM
• All Endress+Hauser GSD files
• Endress+Hauser type files
• Endress+Hauser Bitmap files
• Further helpful information to the units
Working with the GSD/Type files
The GSD files can, dependent on the software being used, either be copied into the programme spe-
cific directory or read into the projecting software data bank using an import function.
Example 1
The directory...\ siemens \ step7 \ s7data \ gsd can be used for the Siemens STEP 7 of the Siemens
SPS S7-300 / 400 projecting software.
Included in the GSD files are also the Bitmap files. The Bitmap files can be used to help in displaying
the measurement points graphically. The Bitmap files must be stored in the directory ...\ siemens \
step7 \ s7data \ nsbmp.
Example 2
If a Siemens S5 is being used and the PROFIBUS-DP network is projected using the COM ET 200
projecting software, then the Type files will be required (x.200 files).
If there are questions regarding other projecting software types, please refer to the PLC manufactu-
rer for the correct directory to be used.
Compatibility of Profile version 2.0 and 3.0 units
One plant can use both Profile 2.0 and 3.0 units using different GSD and a DP master, this is possible
because the cyclic data for the automation system are compatible in both profile versions.
Note!
It is generally possible to exchange similar units with profile version 2.0 with units using Profile ver-
sion 3.0 without exchanging the new projecting.
Note!
An exchange of Endress+Hauser TMD834 temperature head transmitters for the newer TMT184
is possible even though the unit is different in both name and Ident. no.
The TMT184 is accepted as an exchangeable unit, if in the E+H unit matrix of the TMT184 address
V6H0 the change to 'MANUFACT V2.0' is activated ( → chap. 5.2.7). The TMT184 the operates
as a replacement TMD834 with Profile V2.0.