INSTALLATION INSTRUCTIONS
Above a 60cm ATAG oven (HI8071M)
Installation of the induction hob above a combi-microwave, a microwave, a 90 cm
ATAG oven or any other brand of oven.
Ventilation occurs through the plinth and back of the oven. The
niche should be at least 600 mm high.
Make an opening of at least 560 x 6 mm at the front and back.
Saw the ventilation openings in such a way that the total surface
area of the holes is at least 100 cm2. E.g. two holes of 50 cm2.
Fit a shield between the oven and the hob. This shield should be
at least 10 mm thick and heat resistant (85 °C).
The space between the underside of the hob and the shield
should be at least 50 mm.
To protect the airflow, fit a protective panel of the same material
as the shield between the shield and the hob. Ventilation occurs
through the adjacent cupboards.
GB 25

ventilation