Table Digital Read (Code 01); Addresses Table For Bms Implementation - AERMEC AER485 Mode D'emploi

Interface série pour cartes chiller
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Addresses table for BMS implementation

REFERENCE GUIDE FOR MODBUS RTU PROTOCOL
The Modaer communication protocol is the communication
standard made available by Aermec for the connection betwe-
en machines of the chiller series and centralised supervision
or control systems (see the Aermec products guide to see on
which machine this protocol is available).
The protocol allows both the point to point connection (machi-
ne * supervisor), as well as several machines (max 255) on
the same bus link to a supervisor, because it manages one
address for each machine.
The system uses a master-slave communication mode, there-
fore the supervision system is master and the machine slave.
This means that the machine only responds to the enquiry
made by the supervisor.
SERIAL CONFIGURATION:
Below are the addresses foreseen by the protocol and the cor-
responding meaning in terms of the machine. The addresses
that are not listed are reserved or not used and therefore
commands related to addresses that are not listed cannot

Table DIGITAL READ (Code 01)

ID
Data description
0
Standby/On command (toggle) 0=OFF 1=ON
1
Cooling/Heating mode command (toggle) 0=COLD 1=HOT
2
Safety reset command 1=RESET
3
Local/remote command (toggle) 0=LOCAL 1=REMOTE
4
Defrosting status, circuit 1
5
Defrosting status, circuit 2
6
Circuit 1 alarm summary condition
7
Circuit 2 alarm summary condition
8
Flow switch alarm
9
Condenser pump heating alarm
10
Evaporator pump heating alarm
11
Efficiency alarm
12
Circuit 1 compressor heating alarm
13
Low circuit 1 pressure alarm
14
High circuit 1 pressure alarm
15
Circuit 1 antifreeze alarm
16
Circuit 1 fan heating alarm
9600 baud
1 start bit
no parity
1 stop bits
be used as this could lead to the malfunction or breakage
of the machine.
ID
Data description
17
Circuit 1 oil pressure switch alarm
18
Probe alarm circuit 1
19
Circuit 2 compressor heating alarm
20
Low circuit 2 pressure alarm
21
High circuit 2 pressure alarm
22
Circuit 2 antifreeze alarm
23
Circuit 2 fan heating alarm
24
Circuit 2 oil pressure switch alarm
25
Probe alarm circuit 2
26
Voltage monitor alarm
27
Circuit 1 pumpdown alarm
28
Circuit 2 pumpdown alarm
29
Eprom alarm
30
Clock calendar alarm
31
Evaporator pump load
32
Pressure bypass valve load
33
Condenser pump load
34
Circuit 1 compressor load
19