SK 35 Safety Relay
Setting the operating mode via DIP switches
7.
Located underneath the opening on the right side of the housing are six
DIP switches, of which only switches 1 and 2 are assigned a function.
Factory settings are underlined.
S1
Test while voltage is applied (Off) / missing at T1 T2 (On)
S2
Automatic reset (Off) / error lock with man. reset (On)
Automatic reset
(factory setting of S2 = "Off")
Upon rectification of an actuation or fault in the sensor circuits or after a power failure, the SK 35
automatically closes relay contacts 13 14 or 23 24.
During a fault, the corresponding LEDs CH1 / CH2 illuminate constantly.
Error lock with manual reset (S2 = "On")
Upon rectification of a fault in the sensor circuit or after a power failure, the SK 35 does not close
output terminals 13 14 or 23 24 again until contacts Z1 and Z2 are bridged with a button. An auto-
matic restart is thereby rendered impossible. Permanent bridging of contacts Z1 Z2 is not possible
and is detected by the test.
Actuation of the reset push-button always results in the resetting of both
safety related channels!
After the sensor is again released, the corresponding LEDs CH1 / CH2 flash until a man. reset is
performed. During a fault, the corresponding LEDs CH1 / CH2 illuminate constantly.
18
DIP switches