Select the air handling unit according to the technical data and limitations mentioned in the
following table. Lifetime of the outdoor unit, operation range or operation reliability may be
influenced if you neglect these limitations.
Model
GMV-N140U/A-T
GMV-N280U/A-T
GMV-N560U/A-T
Notes:
a)
The capacity of heat exchanger is obtained at these test conditions: evaporation temperature at air outlet of
heat exchanger is 6℃, overheating degree of heat exchanger is 5℃ and the air return temperature is 27℃
DB/19℃WB.
b)
The heat exchanger of air handling unit is designed for R410A, and it's working pressure is 4.2MPa.
c)
Quantity of rows of heat exchanger: no more than 4 rows.
d)
The diameter of copper pipe of heat exchanger is no more than 12.7mm. 9.52mm is recommended.
Notes: The air handling unit can be connected as a standard indoor unit to the outdoor unit.
The limitations of connection are determined by the outdoor unit.
3.4 Selecting the AHU-KIT Unit
The corresponding AHU-KIT unit needs to be selected for your air handling unit. Select the
AHU-KIT unit according to the above limitations.