Let the communication wire go through the rubber ring.
2)
Connect the communication wire to terminal H1 and H2 of indoor 4-bit wiring board.
3)
Fix the communication wire with wire clip on the electric box.
4)
5) Wiring instructions of remote receiving light board and wired controller:
Fig.5.4 shows the installation of wired controller:
5.5 Illuminate for Connection of Wired Controller and Indoor Units
(AHU-KIT) Network
(1) Communication wire of indoor unit and outdoor unit (or indoor unit) is connected to D1,
D2.
(2) Wired controller is connected to H1, H2.
(3) One indoor unit can connect two wired controllers that must be set as master one and
slave one.
(4) One wired controller can control 16 indoor units in maximum at the same time (as shown
in fig.5.5).
Notes:
① The type of indoor units must be the same if they are controlled by the same wired
controller.
② When the indoor unit is controlled by two wired controllers, the addresses of the two
wired controllers should be different through address setting. Address 1 is for main
controller; Address 2 is for slave controller. Detailed settings please refer to the
instruction manual of wired controller.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
OPERATING INSTALLATION MANUAL FOR AHU-KIT UNIT
Fig.5.4
22