Wiring Requirements - Gree GMV-N140U/A-T Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

3.6.2 Select Communication wire for AHU-KIT and Outdoor Unit
Wire Type
Light/Common PVC Jacket
Soft Wire
Light shield/Common PVC
Jacket Soft Wire

3.7 Wiring Requirements

Power Cord Size and Air Switch Capacity:
Model
GMV-N140U/A-T
GMV-N280U/A-T
GMV-N560U/A-T
Notes:
① Use copper wire only as unit's power cord. Operating temperature should be within its
rated value.
② Above selection requirements: Power cord size is based on BV single-core wire (2~4pc)
at 40°Cambient temperature when laying across plastic pipe. Air switch is D type and
used at 40°C. If actual installation condition varies, please lower the capacity
appropriately according to the specifications of power cord and air switch provided by
manufacturer.
③ Install cut-off device near the unit. The minimum distance between each stage of cut-off
device should be 3 mm (The same for both indoor unit and outdoor unit).
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
OPERATING INSTALLATION MANUAL FOR AHU-KIT UNIT
Fig.3.6.2
Total Length of Communication
wire L(m)
L ≤ 1000
L ≤ 1000
Power Cord Size
220~240V/1ph/50Hz &
208~230V/1ph/60Hz
Wire Gauge
2
(mm
)
≥ 2×0.75
≥ 2×0.75
Ground Wire
Air Switch
Minimum Sectional
Capacity(A)
Area(mm
6
1.0
6
1.0
6
1.0
8
Remark
2
If wire gauge is 2X1 mm
,
then it's OK to increase the
length of communication
wire. But total length should
not exceed 1500m.
The shield cable is required
when the unit is installed in
the environment of strong
magnetic or interference.
Power Cord
Minimum Sectional
2
2
)
Area(mm
)
1.0
1.0
1.0

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Gmv-n280u/a-tGmv-n560u/a-t

Table des Matières