VIFB9 - 03/05
2
Configuration
PLEASE NOTE
The cover is connected to the internal PC boards via the
operating voltage cable. It cannot therefore be removed
completely.
CAUTION
The components of the valve terminal contain elements
which are liable to damage by electrostatic charges. The
components can also be destroyed if the contact surfaces of
plug connectors are touched, or if the regulations for hand-
ling electrostatically vulnerable components are not observed.
Please observe the following when configuring:
1. Switch off the operating voltage.
2. Open node (screws are liable to be lost).
3. Set fieldbus address.
4. Set protocol.
5. Close node.
6. If the valve terminal to be connected is at the end of a
fieldbus line, the terminating resistor must be switched on.
Fieldbus baud rate
The Festo valve terminals type 03/05 set themselves auto-
matically to the correct baud rate.