Quality product for HVAC sector, accuracy ± 1.5 % or ± 3 %
The calibratable compact pressure sensors PREMASGARD
with or without optional display (eight devices in one) and are used for measuring above-atmospheric, below-atmospheric, or differential pressures
in air. The piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy. These pressure
transmitters have a pushbutton for manual zero point calibration and an adjustable offset. Applications of these pressure sensors are in clean room,
medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for
level measurement, or for triggering frequency converters. Media measured with these pressure transducers are air (non-precipitating), or other
gaseous non- aggressive, non-combustible media. A PREMASGARD
minimizes the diversity of types and inventory levels while covering a greater range of applications. The differential pressure sensor is supplied
including connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws).
Electronic pressure sensors and switches PREMASREG
continuous output, and a display for setting the switchpoint and to display the ACTUAL pressure (eight devices in one plus differential pressure
switch ⁄ differential pressure monitor and continuous pressure sensor in a single device). The pressure sensor is used for above-atmospheric,
below-atmospheric, or differential pressure measurement in clean air with limit value switching. The piezo-resistive measuring element guarantees a high
degree of reliability and accuracy. Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air conditioning
ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement, or for triggering frequency converters. Media
measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media. The pressure sensor
®
PREMASREG
1141 has a manual zero point pushbutton and an offset potentiometer for final value and switchpoint correction. Fine adjustment by the
user is possible at any time. A connection set ASD-06 (2 m connection hose, two pressure connection nipples, screws) is included in the scope of supply.
TECHNICAL DATA
Power consumption:
Measuring ranges:
Media temperature:
Pressure connection:
Type of pressure:
Medium:
Above- ⁄ below-atmospheric pressure:
Signal filtering:
PREMASGARD
®
1140
Power supply:
Output signal:
Electrical connection:
Accuracy:
Sum of Linearity+hysteresis:
Temperature drift values:
Zero point offset:
®
PREMASREG
1141
Power supply:
Output signal:
Electrical connection:
Accuracy:
Sum of Linearity + hysteresis:
Temperature drift values:
Zero point offset:
Enclosure:
Dimensions:
Electrical connection:
Cable gland:
Humidity:
Protection class:
Protection type:
Standards:
Features:
ACCESSORIES:
®
1141
®
1140 of the 1140 series are equipped with eight switchable measuring ranges and
®
1140 series pressure sensor has eight selectable measuring ranges and therefore,
®
1141 are equipped with eight switchable measuring ranges, one switching output and one
< 1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
multi-range switching with 8 switchable measuring ranges (see table)
0...+ 50 °C
4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm), metal pressure connection nozzles
differential pressure
clean air and other non-aggressive, non-combustible gases
max. ± 200 hPa
switchable 1 s ⁄ 10 s
24 V AC (± 20 %) and 15 ... 36 V DC (± 10 %) for U variant
15 ... 36 V DC (± 10 %) stabilised, max. ripple 0.5 Vss for I variant (depending on working resistance)
0 -10 V or 4 ... 20 mA
2- or 3-wire connection
± 1.5 % of final value (at +20°C) with display (not ± 100 ⁄ 50 Pa)
± 3.0 % of final value (at +20°C) without display (optional ± 1.5 % of final value)
< ± 1 % of final value with display
< ± 2 % of final value without display, standard (optional ± 1 % of final value)
± 0.1 % ⁄ °C with display
± 0.3 % ⁄ °C without display
< ± 0.7 % of final value with display
< ± 1.5 % of final value without display
24 V AC ⁄ DC (± 20 %)
0 -10 V; 1 changeover contact (24 V ⁄ 1 A)
3-wire connection (U)
± 1.5 % of final value (at +20°C)
< ± 1 % of final value
± 0.1 % per °C
< ± 0.7 % of final value
plastic, material polyamide, 30 % glass-globe reinforced, colour traffic white (similar to RAL 9016)
108 x 72.5 x 70 mm (Thor 2)
0.14 - 1.5 mm², via removable plug-in screw terminals
M 16 x 1.5; including strain relief
< 95 % r.H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity, according to EMC directive 2004 ⁄ 108 ⁄ EC, according to EN 61326-1, according to EN 61326-2-3
two-line display with illumination, cutout approx. 36 x 15 mm (W x H), for displaying ACTUAL pressure and ⁄ or
SETPOINT pressure or undercutting or exceeding the measuring range
including connection set ASD - 06 (nipple straight) (included in the scope of delivery)
connection nipple ASD - 07 (at 90 degree angle)
pressure outlet DAL -1 for ceiling or in-wall installation (e.g. in clean rooms)
10