S+S Regeltechnik PREMASGARD 1140 Notice D'instruction page 15

Masquer les pouces Voir aussi pour PREMASGARD 1140:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Manual offset adjustment:
Precondition: DIP switch 6 is in ON position.
Switch must remain in ON position. If switched to OFF, "auto offset" is activated.
See also "Automatic offset setting".
At this setting OFFSET ΔP can be aligned at the potentiometer.
The range for adjustment is ca. ± 10 % of the pressure range.
A different reference point other than the zero point can be used here.
®
1140 / PREMASREG
PREMASGARD
(Range: 0...+ xx Pa)
After successful zero point calibration, the output voltage
is 0 V at 0 Pa pressure difference (with the offset knob
in central position)!
Output voltage 0...10 V
for pressure difference from 0 Pa to final value
1140 / PREMASREG
PREMASGARD
®
(Range: - xx ...+ xx Pa)
After successful zero point calibration, the output voltage
is 5 V at 0 Pa pressure difference (with the offset knob in
central position)!
Output voltage 0...10 V
for pressure difference - ΔP... +ΔP
®
1141
®
1141
®
PREMASGARD
1140
(Range: 0...+ xx Pa)
After successful zero point calibration, the output current
is 4 mA at 0 Pa pressure difference (with the offset knob
in central position)!
Output current 4...20 mA
for pressure difference from 0 Pa to final value
PREMASGARD
®
1140
(Range: - xx ...+ xx Pa)
After successful zero point calibration, the output current
is 12 mA at 0 Pa pressure difference (with the offset knob
in central position)!
Output current 4...20 mA
for pressure difference - ΔP... +ΔP
15

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Premasreg 1141Premasgard 114 série

Table des Matières