G
®
THERMASGARD
The top hat rail measuring transducer THERMASGARD
according to DIN 60751, with 13 switchable measuring ranges (selectable via DIP switches). It is installed inside control cabinets or distribution
boxes. The top hat rail transmitter converts the sensor's temperature-dependent resistance signal into a standard signal of 0 - 10 V or 4...20 mA.
The output signal is highly accurate temperature linear. The measuring transducer is factory-calibrated.
TECHNICAL DATA
Output:
Power supply:
Power consumption:
Input:
Testing current:
Zero point:
Range:
Sensor breakage:
Short circuit:
Residual ripple permissible:
Output:
Response time:
Operating temperature:
Enclosure:
Protection class:
Protection type:
Standards:
®
THERMASREG
HSM – Top hat rail measuring transducers for temperature
Type ⁄ WG01
HSM - I
H S M - I
HSM - U
H S M - U
Extra charge:
For special orders
please specify:
HSM
®
HSM is an analogue temperature measuring transducer for Pt100 or Pt1000 sensors
0 - 10 V
24 V AC ⁄ DC ±10 %
< 0.2 VA ⁄
24 V AC ⁄ DC
Pt100 ⁄
Pt1000
0.25 mA
–200...+830 °C
> +20 °C
> 10 V
0 V
< 10 %
0 -10 V
min. load resistance
3 k Ohm
< 0.1 s
-40...+85 °C
2TE (75 x 25 x 53 mm)
material polycarbonate,
colour signal green (similar to RAL 6029)
III (according to EN 60 730)
IP 20 (according to EN 60 529)
CE conformity, electromagnetic compatibility
according to EN 61 326,
EMC directive 2014 ⁄ 30 ⁄ EU
Sensor
Pt100 ⁄ Pt1000
Pt100 ⁄ Pt1000
Other ranges optional
Type and measuring range (MR)
e. g. HSM- U, Pt100, (MR: 0 ...+ 450 °C); HSM- I, Pt100, (MR: 0 ...+550 °C)
4...20 mA
24 V DC
< 0.55 VA ⁄
24 V DC
Pt100 ⁄
Pt1000
0.25 mA
–200...+830 °C
> +20 °C
> 20 mA
< 4 mA
< 10 %
4...20 mA
max. working resistance
Ra (Ohm) = UB -12 V ⁄ 0.02 A
< 0.1 s
-40...+85 °C
Output
4...20 mA
0 - 10 V
Rev. 2017 - V12 GB
Item No.
IP 20, I - variant
1101-6112-0009-700
IP 20, U - variant
1101-6111-0009-700