Display readout:
PREMASGARD
®
1140
st
line the actual pressure is indicated up to
In the display in the 1
the measuring range limit.
Switching between the units Pa and hPa (100 Pa = 1 hPa) happens
automatically. Characters displayed:
Pa = pascal
hP = hectopascal
PREMASREG
®
1141
In the display in the 1
st
line the actual pressure is indicated up to
the measuring range limit.
Switching between the units Pa and hPa (100 Pa = 1 hPa) happens
automatically. Characters displayed:
Pa = pascal
hP = hectopascal
In the 2
nd
line information regarding the relay switching status is
visible (in form of a circle) as well as an indication of the pressure
switchpoint in Pa (adjustable via set potentiometer).
Circle empty = relay in idle state
Circle solid
= relay activated
®
1140 / PREMASREG
PREMASGARD
Indication of range exceedance respectively underrunning
When the pressure range is exceeded or underrun, the limit
exceedance is indicated in the 2
The exceeded pressure range is depicted blinking in Pa, showing
the direction of overrunning.
DIP switches for
pressure range setting, output attenuation and zero compensation:
Pressure range
(adjustable, maximum measuring range depending on type of device)
0...1000 Pa
0...5000 Pa
0...100 Pa
0...1000 Pa
0...300 Pa
0...2000 Pa
0...500 Pa
0...3000 Pa
0...1000 Pa
0...5000 Pa
Measuring range mode
(Mode selectable)
Unidirectional ( 0 ...+MR )
Bidirectional (–MR ...+MR )
®
1141
nd
display line.
–100...+100 Pa
–1000...+1000 Pa
–50...+50 Pa
–100...+100 Pa
–100...+100 Pa
–300...+300 Pa
0 ... +50 Pa
–500...+500 Pa
0 ...+100 Pa
–1000...+1000 Pa
Output damping
DIP 3
(Strength and length-adjustable)
OFF
Long (10 s)
O N
Small (1 s)
Automatic offset setting:
Contact
pin side
Plug for
display
ON
1 2 3 4 5 6
DIP- switches
1 2 3 4
1. For zero point setting, the device must be in operation for at least
60 minutes.
2. Connect pressure inputs P (+) and P (–) with a hose.
(Pressure difference between the inputs = 0 Pa).
3. Precondition: DIP switch 6 is in OFF position.
4. For zero point setting, press pushbutton uninterrupted for 10
seconds.
By pressing the pushbutton, a countdown of ca. 10 seconds is
started. The yellow LED is blinking and the countdown is shown on the
display (optional).
Zero point calibration takes place after the countdown period. This is
indicated by continuous LED light and at the display (optional) by
switching from "AUTO 0" to "PROG 0".
Note: By releasing the pushbutton during the countdown
(counter > 0), zero point setting is immediately cancelled!
–5000...+5000 Pa
–1000...+1000 Pa
–2000...+2000 Pa
–3000...+3000 Pa
–5000...+5000 Pa
DIP 4
OFF
O N
14
min. max.
Pushbutton
Zero point setting
Offset
(auto zero)
Plug for display
auto
DIP
zero
Offset correction
LED
see graph
Offset
ca. ± 10%
PREMASGARD
is not assigned!
DIP 1
DIP 2
OFF
OFF
O N
OFF
OFF
O N
O N
O N
Zero point calibration
(Function adjustable)
Pushbutton (auto zero)
Potentiometer (offset)
®
1140
DIP switch 5
DIP 6
OFF
O N