G
®
THERMASGARD
Calibratable tube contact temperature measuring transducer THERMASGARD
sensor, continuous output, rugged housing made from stainless steel V4A, with cable gland or M12 connector according to DIN EN 61076-2-101.
The surface-contact sensor is used for temperature detection on lines, pipes (e.g. cold and hot water) or on heating sections for heating system
control. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

TECHNICAL DATA

Power supply:
Working resistance:
Load resistance:
Power consumption:
Insulating resistance:
Sensor:
Measuring ranges:
Deviation, temperature:
Output:
Connection type:
Electrical connection:
Cable connection:
Housing:
Housing dimensions:
Connecting cable:
Sensor protection:
Strap dimensions:
Process connection:
Ambient temperature:
Permitted humidity:
Protection class:
Protection type housing:
Protection type sensor:
Standards:
®
THERMASGARD
HFTM - VA
Type ⁄ WG02I
ALTM 2 - VA
A LT M 2 - I VA
A LT M 2 - U VA
Housing variant:
ALTM 2 - VAQ
A LT M 2 - I VA Q
A LT M 2 - U VA Q
Housing variant "Q":
Extra charge:
ALTM2 - VA ID
24 V AC ⁄ DC (± 10 %) for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
R
(ohm) = (U
-14 V) ⁄ 0.02 A for I variant, see working resistance diagram
a
b
R
> 5 kOhm for U variant
L
< 1.0 VA ⁄ 24 V DC; < 2.2 VA ⁄ 24 V AC
≥ 100 MΩ, at +20 °C (500 V DC)
Pt1000, DIN EN 60751, class B
(Perfect Sensor Protection with IP68) Sensor external
multi-range switching with 8 switchable measuring ranges
see table (other ranges optional)
T
above +100 °C, operating range –50...+150 °C
max
with manual zero point correction (± 10 K)
typically ± 0.2 K at +25 °C
0 - 10 V or 4... 20 mA
2-wire connection
0.14 - 1.5 mm², via screw terminals
cable gland, stainless steel V2A (1.4305)
(M 20 x 1.5; with strain relief, exchangeable,
inner diameter 6 - 12 mm) or
M12 connector (male, 5-pin, A-code)
according to DIN EN 61076-2-101
stainless steel V4A (1.4571), with non-distortion cover bolting,
impact-resistant, high EMI shielding,
corrosion, temperature, weather- and UV-resistant
143 x 97 x 61 mm (Tyr 2E)
Silicone, SiHF, 2 x 0.25 mm²; KL = 1.5 m
(optionally also other lengths and measuring range limits, e.g., PTFE up to +250 °C or
glass fibre with steel mesh up to +350°C)
pipe feeder, stainless steel V4A (1.4571), Ø = 6 mm,
nominal length NL = 50 mm, cable entry stamped
Ø = 13 - 92 mm (¼ - 3"), L = 300 mm
endless strap in metal tightener
(included in the scope of delivery)
measuring transducer –30...+70 °C
< 95 % r. H., non-precipitating air
III (according to EN 60 730)
IP 65 (according to EN 60 529) Housing tested,
TÜV SÜD, Report No. 713160960B (Skadi2)
IP 65 (according to EN 60 529) sleeve humidity-tight (standard)
IP 68 (according to EN 60 529) sleeve water-tight (optional)
CE conformity, electromagnetic compatibility according to EN 61326, according to EMC Directive 2014 ⁄ 30 ⁄ EU
Surface contact ⁄ tube contact temperature measuring transducers, ID
Stainless steel housing
Sensor
Output
Pt1000
4...20 mA
Pt1000
0 -10 V
Cable connection with cable gland
Pt1000
4...20 mA
Pt1000
0 -10 V
Cable connection with M12 connector (male, 5-pin, A-code)
other measuring ranges optional
Protection type IP 68 (Sensor sleeve watertight compound-filled)
2-wire connecting leads, per running meter (silicone / PTFE / glass fibre)
®
ALTM 2 - VA with eight switchable measuring ranges, external
Type
Remote sensor
Remote sensor
Remote sensor
Remote sensor
Rev. 2020 - V13
= Q
Item No.
2001- 2151- 2200-001
2001- 2151- 1200- 001
2001- 2151-2100- 001
2001- 2151-1100- 001
on request