Boiler Exhaust Vent Hanger And Support (Rigid Pipes) - Rinnai E60SRN Instructions D'installation Et D'entretien

Masquer les pouces Voir aussi pour E60SRN:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6.7.2 d

Boiler Exhaust Vent Hanger and Support (Rigid Pipes)

The purpose of this section is to provide more information about Rinnai's requirement
that the vent system installed with the Rinnai boiler must be appropriately supported.
As we state elsewhere in this manual, "place pipe supports every 4 feet (1219 mm)
of horizontal run, beginning with the support near the boiler to prevent movement in
fittings and allow boiler to be free from any strain or weight on boiler or fittings." For
Horizontal pipes, the first support should be placed as close as possible after the first
elbow. These required vent supports are critical to prevent movement in fittings and
to allow the boiler to be free from any strain or weight associated with the installed
fittings and/or vent pipe system.
Installation of the venting system MUST comply with the respective vent manufacturer's
instructions. Additionally, to ensure structural integrity, the installer MUST select
hangers, supports, and restraints which are able to withstand all static and dynamic
loading conditions which act upon the vent piping system and the associated Rinnai
boiler. Hangers, supports, and restraints shall be 100% corrosion proof, UV resistant,
and impact resistant.
Exhaust vent pipe MUST be securely fastened to the structure to avoid movement.
The first hanger support MUST be located directly after the first elbow on the first
horizontal vent section or as close thereto as possible to ensure no movement. (see
example below). Use hangers that will not score or damage vent pipes and are
accepted by local codes.
figure 13M
Recommended pipe hanger and support for PVC/CPVC pipes
The information provided is an effort to assist you in better understanding the
requirements to secure the venting. This document has been compiled from generally
accepted engineering principles and standards from the American National Standards
Institute and other pertinent documents. The specifications herein are intended as
a guide only and it is the responsibility of the engineer/designer or installer to select
appropriate support and to use this guide in conjunction with all applicable codes
and/or standards.