External activation connection
There is the possibility to activate the charger using an external signal (e.g.
from a home automation system or from a prepaid system). This signal is
priority over any other load activation system; therefore if the external activation
is activated, charging would start when the vehicle is connected to the charger.
To access the connection, the protection plate must be removed from the
circuit. The connection must be done by closing the INAX3 and VCC5 inputs of
the X91 connector with a potential-free external circuit as shown in the
following image. To access the connection, the protection plate must be
removed from the circuit.
External extractor connection
The vehicle when it is heated and has internal fans goes to state D, which is to
say activates its internal fans indicating that it will generate heat. That heat in a
closed garage must be evacuated by an extractor. The VIARIS charger, when
detecting the D state, activates a potential-free contact to be able to connect an
extractor with a maximum consumption of 5 A. In the event that the VIARIS
charger had two sockets, this functionality is associated only with the
base/connector 1. The connection must be made on the two outputs marked as
AUX-1 of the X5 connector, as shown in the following image.
AUX-1
AUX-1
13