To configure the rated power of the installation, manually adjust the circuit
indicated in the following image.
The position of the rotary circuit defines the maximum current of the
installation, this parameter must be configured according to the rated power in
the installation as shown in the following table.
This adjustment is fundamental for the correct operation of the load modulator.
If the
transformer is not installed, the position of the rotary circuit
TMC100
must be in position NO LIMIT. in order not to limit the load current.
Single-phase
Current/Power
Unlimited
10 A/2.3 kW
13 A/3 kW
15 A/3.45 kW
18 A/4.14 kW
20 A/4.6 kW
23 A/5.3 kW
25 A/5.75 kW
28 A/6.44 kW
30 A/6.9 kW
35 A/8.05 kW
40 A/9.2 kW
45 A/10.35 kW
50 A/11.5 kW
55 A/12.65 kW
63 A/14.49 kW
Three-phase
Current/Power
Unlimited
10 A/6.928 kW
13 A/9 kW
15 A/10.392 kW
18 A/12.42 kW
20 A/13.856 kW
23 A/15.9 kW
25 A/17.321 kW
28 A/19.32 kW
30 A/20.785 kW
35 A/24.249 kW
40 A/27.713 kW
45 A/31.177 kW
50 A/34.641 kW
55 A/37.95 kW
63 A/43.648 kW