Design Envelope 4302 ivs et 4382 ivs Groupe de
pompage vertical en ligne avec commandes intégrées
Pump won't
Start
no
Is the Keypad
display and
on led lit?
Check 3 phase
mains supply
no
Is the Link
made on x101
t3 to t6?
Connect x101
t3 to t6
no
Is a start
signal applied
to x101 t4?
Check remote
start signal or
link x101
t4 to t6
no
Is the reference
signal on x101 t2
Check remote
reference
signal from
bms
Press the Key
pad start key
See the alarm
descriptions on
page 17/18
yes
Is the
no - bms
pump being used
in Sensorless
Mode?
Connect x101
yes
t3 to t6
Check remote
start signal or
yes
link x101
t4 to t6
yes
>0vdc?
Has the keypad
stop key been
Yes-
pressed?
Display
Flashing
yes
Does the
display show
an alarm?
Contact
Armstrong Service
Department
Instructions d'installation
et d'utilisation
yes
no
Is the Link
made on x101
t3 - t6?
yes
no
Is a start
signal applied
to x101 t4?
yes
no
no
29