Safety Guidelines

1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2

Technical Data

Media
Medium:
Connections/Sizes
Flange connection
Single filter:
2 filters parallel:
Pressure values
Max. operating pressure:
Nominal pressure:
Operating temperatures
Max. operating temperature
medium accord. to EN 1567:
Max. operating temperature
medium:
Specifications
Installation position:
Note:
The filter is constructed for drinking water installations. In
case of a process water application the filter has to be
proven individually.
3
Options
For Options visit homecomfort.resideo.com/europe
4
Assembly
4.1 Installation Guidelines
Install in horizontal pipework with filter bowl
downwards
– This position ensures optimum filter efficiency
Install shut-off valves
Drinking water
PN16 acc. to EN 1092-2
DN65 - DN100
DN125 with 2 extension
flanges EXF125-A
2 x DN80, 2 x DN100
1.5 - 16 bar
PN16
30 °C
65 °C (max. operating
pressure 6 bar)
Horizontal, with filter bowl
downwards
GB
These filters are armatures which need to be
maintained regularly
Ensure good access
– Pressure gauge can be read off easily
– Simplifies maintenance and inspection
The installation location should be protected against
frost
Related to the EN 806-2 it is recommended to install
the filter immediately after the water meter
In order to avoid flooding, it is recommended to
arrange a permanent, professionally dimensioned
wastewater connection
4.2 Assembly instructions
1.
Thoroughly flush pipework
2.
Install filter
• Note flow direction
• Install without tension or bending stresses
3.
Seal in pressure gauges
4.
Install discharge connection
4.3 Discharge of reverse rinsing water
CAUTION!
According to EN1717 the space between bottom
from discharge connection at the filter and the
sewage piping (e.g. drain connection with syphon)
has to be 56mm at least.
To do this there are 3 options:
1.
Discharge into floor drain
2.
Drain into open container.
3.
Discharge into drain connector with syphon (min.
DN70)
Filter size
DN65 - 100
*at 4 bar inlet pressure and 22 s reverse rinsing duration -
operated by actuator or at 4 bar inlet pressure and 3x 3 s
rinsing duration - operated by hand.
5
Operation
CAUTION!
Filter may only be operated with installed discharge
connection.

5.1 Reverse rinsing

At the latest every 6 months, reverse rinsing should be carried
out according to EN 806-5. Our recommendation at least
every 2 months.
Red pointer integrated into the view window of one of
the pressure gauges for setting the next reverse
rinsing
2
Reverse rinsing volume*
55 litre
MU1H-1178GE23 R0320