Safety Guidelines; Technical Data - resideo Braukmann D06F Instructions D'installation

Masquer les pouces Voir aussi pour Braukmann D06F:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 11
1

Safety Guidelines

1.
Follow the installation instructions.
2.
Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3.
Note that the appliance is exclusively for use in the
applications detailed in these installation instructions
(see 2 Technical Data). Any other use will not be
considered to comply with requirements and would
invalidate the warranty.
4.
Please take note that any assembly, commissioning,
servicing and adjustment work may only be carried
out by authorized persons.
5.
Immediately rectify any malfunctions which may
influence safety.
2

Technical Data

2.1 D06F
Media
Medium:
Connections/Sizes
Connection sizes:
Nominal sizes:
Pressure values
Max. inlet pressure with clear
filter bowl:
Max. inlet pressure with brass
filter bow:
Outlet pressure:
Preset outlet pressure:
Min. pressure drop:
Operating temperatures
Max. operating temperature
medium (10 bar/brass filter
bowl):
Max. operating temperature
medium accord. to EN 1567:
Note:
Use the SM06T brass filter bowl, if the valve can be
exposed to UV radiation or solvent vapors.
2.2 D06F-LF
Media
Medium:
Connections/Sizes
Connection sizes:
Nominal sizes:
MU1H-1002GE23 R0120
Drinking water
1
/
" - 2"
2
DN15 - DN50
16 bar
25 bar
1.5 - 6 bar
3 bar
1 bar
70 °C
30 °C
Drinking water
1
/
" - 2"
2
DN15 - DN50
Pressure values
Max. inlet pressure with clear
filter bowl:
Outlet pressure:
Preset outlet pressure:
Min. pressure drop:
Operating temperatures
Max. operating temperature
medium accord. to EN 1567:
Note:
Use the SM06T brass filter bowl, if the valve can be
exposed to UV radiation or solvent vapors.
2.3 D06FH
Media
Medium:
Connections/Sizes
Connection sizes:
Pressure values
Max. inlet pressure:
Outlet pressure:
Preset outlet pressure:
Min. pressure drop:
Operating temperatures
Max. operating temperature
medium (10 bar):
Max. operating temperature
medium accord. to EN 1567:
2.4 D06FN
Media
Medium:
Connections/Sizes
Connection sizes:
Nominal sizes:
Pressure values
Max. inlet pressure:
Outlet pressure:
Preset outlet pressure:
Minimum pressure:
Operating temperatures
Max. operating temperature
medium (10 bar):
Max. operating temperature
medium accord. to EN 1567:
5
16 bar
1.5 - 6 bar
3 bar
1 bar
30 °C
Drinking water
1
/
" - 2"
2
25 bar
1.5 - 12 bar
5 bar
1 bar
70 °C
30 °C
Drinking water
1
/
" - 2"
2
DN15 - DN50
25 bar
0.5 - 2 bar
1.5 bar
0.5 bar
70 °C
30 °C

Publicité