4. Technical data

4.1 Application limits

4.1.1 Ambient temperature limitation

Chiller is designed to operate in the ambient temperature range indicated on the type label. When ambient
temperatures are out of that range, manufacturer must be consulted.

4.1.2 Voltage limitations

According to CEI EN 60204-1, Pfannenberg standard chiller operation is guaranteed within these ranges:
Nominal voltage ±10 % [V]
Nominal frequency ±1 %
Please refer to the type label to see the nominal operating conditions of the unit.
Nominal conditions
230 V / 1 ~ / 50 Hz
230 V / 1 ~ / 60 Hz
400 V / 3 ~ / 50 Hz
460 V / 3 ~ / 60 Hz
NOTICE
Special voltage
For units with special voltages please refer to the type label.

4.2 Type label

This is an example of a type label.
Important is the information of the chiller serial number, which is needed for all technical questions.
Operating and Maintenance Instructions - Chiller - Series EB 210 - EB 440
[Hz]
V min [V]
V max [V]
207
207
360
414
f min [Hz]
253
49.5
253
59.4
440
49.5
506
59.4
© Pfannenberg GmbH
f max [Hz]
50.5
60.6
50.5
60.6