Sommaire des Matières pour Pfannenberg CCE Standart Serie
Page 1
CCE Standard series CCE 6101 - CCE 6201 - CCE 6301 - CCE 6401 - CCE 6501 - CCE 6601 MANUFACTURER DASSI S.r.l. – Member of the Pfannenberg Group Via La Bionda, 13 I-43036 Fidenza (PR) Tel. +39 0524-516711 Fax. +39 0524-516790 E-mail: info@pfannenberg.it...
Page 2
Tel: +86-512 6287 1078 –Fax: +86-512 6287 1077 info@pfannenberg.cn - www.pfannenberg.cn Pfannenberg Asia Pacific Pte Ltd 61 Tai Seng Avenue # B1-01 UE Print Media Hub ASIA Singapore 534167 info@pfannenberg.com www.pfannenberg.com For Service, please contact the nearest Pfannenberg Service Company 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 3
English Index Warranty .....................................4 Safety ....................................4 Residual risks ..................................6 Receiving and Unpacking ..............................6 Positioning the Chiller ................................7 Connections ..................................8 7. Voltage Limitations: ................................10 Process Water / Fluids ..............................10 Waterquality ................................... 11 Ambient temperature ................................ 12 Start up of the chiller ............................... 12 Decommissioning, disposal .............................
Page 4
English 1. Warranty For informations about warranty please visit Pfannenberg website: http://www.pfannenberg.com/en/company/general-conditions/ 2. Safety The Chiller instructions must be read by the installer and personnel in charge for operation, before starting the chiller. All safety and security instructions given in this manual have to be observed! Only qualified personnel are allowed to install, operate and do the maintenance work.
Page 5
English rotating fans Always disconnect power supply and make sure all mechanical equipment is stopped before service. Toxicity of refrigerant and It is recommended to use suitable cooling liquid protection equipment (such as gloves, glasses, safety shoes) *NOTE: for environmental reasons never discharge refrigerant into atmosphere (follow local regulations to properly dispose of refrigerant).
Page 6
If you need any consultancy in terms of a maintenance and leakage check according (EU) No. 517/2014 please contact our Pfannenberg Service Team. To ensure the proper and reliable functionality of the chiller, we recommend to perform the commissioning by our Pfannenberg Service Team.
Page 7
For regular maintenance or adjustment, the chiller shall be located between 0,3 m and 1,0 m above the servicing level. PFANNENBERG chillers should be set on a concrete slab. The slab should extend a minimum of 30cm (12 inches) beyond the perimeter of the Chiller to prevent damage from lawn maintenance equipment, etc. The Chiller, which should be level and properly anchored, is provided with 4 antivibration dampers on the bottom of the unit, which allow the support and the fixing of the Chiller and to dampen the vibrations and decrease the noise during the operation.
Page 8
English Connections WARNING: Hydraulic connections are the first ones to be assembeled during installing operation, to be followed by electric connections. Remove the caps inside the hydraulic fittings connection before to connect the chiller to your device. WARNING: The chillers has been cleaned by means of specific cleaning products. eventual findings of solid particles in the hydraulic system might cause the loss of warranty.
Page 9
Check that the voltage and frequency of the power supply correspond to the specifications on the unit’s data plate and/or enclosed electrical plan. • Pfannenberg Chiller units are designed for TN Earthing Systems. Use the Maximum fault loop Chiller Impedence value for sizing purposes on site (refer to Zpe value specified within Electrical Diagram attached) •...
Page 10
For units with special voltages please refer to the type label. Process Water / Fluids PFANNENBERG chillers should be filled to the proper level with an inhibited glycol designed for Industrial chillers systems. Do not use automotive antifreeze! The inhibitors used in automotive antifreeze can break down quickly and accelerate the degradation of the coolant base (glycol);...
Page 11
Do not allow biological, slime bacteria, and algae contamination. If this does happen, treat the water with biocides. PFANNENBERG recommends that the properties of the water has to be checked in order to identify the quality Water quality A (No water treatment necessary):...
Page 12
English 9. Ambient temperature Chiller is designed to operate in the ambient temperature range indicated in the type label. When ambient temperatures areout of that range, manufacturer must be consulted. High ambient temperatures reduce Chiller capacity. Low ambient temperatures require special controls. Fluid heaters may be required to prevent freezing and to hold the fluid in the Chiller reservoir at constant temperature in order to reduce start-up delays while the fluid warms up to operating temperature.
Page 13
English • Fill reservoir with water-glycol mixture until the maximum level is reached. (water quality and treatment should be established according to the application specifications) Picture 10 – Max visual level • Establish main power feed and alarm cable with customer’s equipment. When units are provided without power and alarm cables (or industrial connectors), cable on terminal blocks into the electrical box, according to the e-plan enclosed with the unit.
Page 14
English Picture 13 – Main switch ON CAUTION: The pump must not flat running or in inverse direction; therefore the checking of the correct rotation must be quick • Switch on the pump; the fluid level must always stay over the miminum level. After the water circuit has run for approx.
Page 15
Refrigerant must be professionally extracted from the refrigerant system. Avoid refrigerant emissions. The unit must only be disposed of by authorized, qualified personnel. Waste equipment must also be disposed of correctly by Pfannenberg. Freight charges for delivery to one of our manufacturing facilities must be pre-paid. 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 16
English Debug Table The information described below are useful for the service staff. The faults that require the intervention of a refrigeration engineer must be carried out only by specialized staff. Follow all electrical legislation when working on the unit based on valid laws of the countries were the unit is placed.
Page 17
English • Replace the fan The fan is broken Verify the connection on the terminal board of the electrical box; Check the • right rotation of the electrical motor (only 3 phase version) Wrong fan rotating direction Check that the chiller is located in a place that can guarantee suitable •...
Page 18
English 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 19
English APPENDIX A1 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 20
English APPENDIX B1 Maintanace / Check and Inspections CAUTION: Before any maintenance intervention, not needing the machine running, disconnect the supply voltage and put the signal MAINTENANCE IN PROGRESS next to the lockable main switch in “Off” position. Carrying out the tests and check program listed below will extend the life of the equipment and avoid possible breakdowns.
Page 21
English • Inspect the condenser monthly on the external side to see if it is clean. The fins of the condenser must not have any dust deposits or residual products or sludges on their surface . Picture 20 – Condenser external surface Picture 21 –...
Page 22
English APPENDIX B2 Electrical and mechanical components Rrefrigeration and hydraulic circuits are accessible by removing the two lateral panels. Compressors CCE 6101 – 6201 - 6301 Compressors CCE 6401 – 6501 - 6601 Dehydrator Filter High pressure switch Condenser Thermostatic Valve Evaporator Pump 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 23
CCE Standard Serie CCE 6101 - CCE 6201 - CCE 6301 - CCE 6401 - CCE 6501 - CCE 6601 HERSTELLER DASSI S.r.l. – Member of the Pfannenberg Group Via La Bionda, 13 I-43036 Fidenza (PR) Tel. +39 0524-516711 Fax +39 0524-516790 E-Mail: info@pfannenberg.it...
Page 24
Tel: +86-512 6287 1078 –Fax: +86-512 6287 1077 info@pfannenberg.cn - www.pfannenberg.cn Pfannenberg Asia Pacific Pte Ltd 61 Tai Seng Avenue # B1-01 UE Print Media Hub ASIEN Singapore 534167 info@pfannenberg.com www.pfannenberg.com Für den Kundendienst wenden Sie sich bitte an das Pfannenberg- Kundendienstunternehmen in Ihrer Nähe. 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 25
Deutsch Inhaltsverzeichnis Garantie .................................... 26 Sicherheit ..................................26 Restrisiken ..................................28 Empfang und Auspacken ..............................29 Positionierung des Rückkühlers ............................30 Anschlüsse ..................................31 Wasser / Kühlflüssigkeiten ............................... 32 Wasserqualität ................................33 Umgebungstemperatur ..............................34 Inbetriebsetzung des Rückkühlers ............................ 34 Außerbetriebnahme, Entsorgung .............................
Page 26
Deutsch 1. Garantie Informationen zur Gewährleistung erhalten Sie bitte auf unserem Website Pfannenberg http://www.pfannenberg.com/de/unternehmen/agb/ 2. Sicherheit Der Installateur und das für den Rückkühler zuständige Personal müssen diese Anleitungen vor der Inbetriebsetzung der Maschine lesen. Alle in diesem Heft enthaltenen Sicherheitsanleitungen beachten.
Page 27
Deutsch Stromschlag Die Stromversorgung immer abtrennen. Während der Arbeiten am Gerät ein Schild mit der Warnung ACHTUNG WARTUNGSARBEITEN gut sichtbar neben dem Hauptschalter anbringen. Sich drehende Lüfter Vor Arbeiten an der Maschine immer die Stromversorgung abtrennen und sicherstellen, dass alle mechanischen Apparate ausgestellt sind.
Page 28
Originalersatzteile von KKT chillers zu verwenden. Sie sichern somit die Zuverlässigkeit und die Qualität der Maschine. Für Anfragen zu Ersatzteilen wenden Sie sich bitte an unser Pfannenberg Service Team (Kontaktdaten, S.34). Für eine Beratung und eine auszuführende Wartung und Dichtigkeitsprüfung (gem. EU Verordnung 517/2014), wenden Sie sich bitte an den Pfannenberg Service.
Page 29
Bestandteile beschädigen könnten. In der Standard-Ausführung (über 45 kg Gewicht) können die Kühlanlagen der Firma PFANNENBERG mit vier Ösenschrauben zum Anheben und Transportieren versehen werden; diese dürfen nur zum vertikalen Auf-/Abladen eingesetzt werden (die richtigen Stellen zum Anheben der Anlage sind mit Aufklebern gekennzeichnet).
Page 30
0,3 m bis 1,0 m über der Höhe, in der sich die Wartungsvorrichtungen befinden, zu positionieren. Die PFANNENBERG-Rückkühler müssen auf einer Fundamentplatte aus Beton aufgestellt werden, die mindestens 30 cm über den Umriss des Rückkühlers überstehen muss, um Beschädigungen (zum Beispiel durch Geräte zur Pflege der Grünflächen usw.) zu vermeiden.
Page 31
Deutsch Anschlüsse ACHTUNG! Bei der Installation sind zuerst die Hydraulikanschlüsse, dann die elektrischen Anschlüsse zu erstellen. ACHTUNG! Die Kältemaschinen wurde durch spezifische Reinigungsmittel gereinigt worden ist. Die eventuelle Erkenntnisse von Feststoffpartikeln im Hydrauliksystem kann dazu führen, den Verlust der Garantie. Hydraulikanschlüsse.
Page 32
Sicherstellen, dass Versorgungsspannung und -frequenz mit den Angaben auf dem Kennschild der Einheit und/oder auf dem beigefügten Schaltplan übereinstimmen. • Die Pfannenberg-Rückkühler wurden für Erdungsanlagen des Typs TN entwickelt. Für die Dimensionierung vor Ort ist der max. Impedanzwert des Rückkühler-Störkreises zu verwenden (siehe im beigefügten Schaltplan spezifizierter Wert Zpe).
Page 33
Korrosionsschutz: PFANNENBERG empfiehlt den Gebrauch von Glykol Pfannenberg Protect auch als korrosionshemmendes Mittel. Der Glykolanteil an der Mischung hängt von der niedrigsten Betriebstemperatur der Mischung ab (die mit dem für die Einheit eingestellten niedrigsten Betriebswert übereinstimmen muss – siehe Technisches Datenblatt der Einheit): Propylenglykol Verdünnung...
Page 34
Der biologischen Verunreinigung durch Myxobakterien und Algen vorbeugen. Wenn es zu einer solchen Verunreinigung kommt, ist das Wasser mit Bioziden zu behandeln. PFANNENBERG empfiehlt die Wassereigenschaften zu prüfen, um die Güte des Wassers zu bestimmen. Wasser Güteklasse A (keine Behandlung erforderlich): Trinkbares Leitungswasser, frei von Verunreinigungen pH:7-9 Härte:<5°dH...
Page 35
Deutsch • Den Hauptschalter, den Steuerschalter und alle Trennschalter auf „0“ (Off) stellen. Abbildung 7 – Hauptschalter OFF Abbildung 8– Trennschalter OFF • Wasserein- und -auslassleitungen anschließen. • RÜCKKÜHLER mit Tank: Den Stopfen des Befüllstutzens am Oberteil/Vorderseite des Rückkühlers (außen) oder an der oberen Tankplatte (innen) entfernen.
Page 36
Deutsch • RÜCKKÜHLER mit Pumpe: Den Hauptschalter und den Trennschalter der Pumpe (oder der Pumpen) auf „On“ stellen. (alle anderen Trennschalter sollten auf „Off“ bleiben) Abbildung 12 – Pumpenschalter auf ON • RÜCKKÜHLER mit Pumpe: Den Hauptschalter auf „I“ (On) stellen und prüfen, dass die Drehrichtung der Pumpe (oder der Pumpen) richtig ist.
Page 37
Nach Abschluss der Installation benötigt der RÜCKKÜHLER keine Eingriffe durch einen speziell ausgebildeten Bediener. Die Kalibrierung der Thermostate, des Druckwächters und aller anderen Komponenten des Kühlkreislaufs hat ausschließlich durch den Kundendienst Pfannenberg. Für weitere Informationen bezüglich Installation des Rückkühlers, Inbetriebsetzung oder Behebung von Störungen ist PFANNENBERG zu kontaktieren.
Page 38
Das Kältemittel muss fachgerecht aus dem Kältemittelkreis abgesaugt werden. Kältemittelemissionen vermeiden. Der Chiller darf nur von autorisiertem Fachpersonal entsorgt werden. Auch Altgeräte müssen von Pfannenberg ordnungsgemäß entsorgt werden. Frachtkosten für die Lieferung an eine unserer Produktionsstätten müssen im Voraus bezahlt werden. Tabelle zur Lokalisierung der Störungen...
Page 39
Deutsch Die in diesem Kapitel enthaltenen Informationen sind für das Kundendienst- und Wartungspersonal bestimmt. Die Störungen, die den Eingriff eines Kühltechnikers erfordern, können nur von Fachpersonal behoben werden. Bei Eingriffen an der Einheit sind alle Vorschriften in Sachen elektrische Anlagen und Gesetze des Landes zu befolgen, in dem die Einheit installiert ist.
Page 40
Deutsch • Zur Beachtung: Nach dem Beheben der Störungsursache der Rückkühler durch Drücken des Reset-Druckknopfs am Außenkörper des Druckwächters einschalten (siehe Abbildung) Kompressor Störung Ursache Mögliche Maßnahme zur Behebung Der Kompressor bleibt ständig in Betrieb und dem Rückkühler gelingt es nicht, die Flüssigkeitstemperatur unter Kontrolle zu halten: Die Temperatur der Flüssigkeit ist zu niedrig Die Temperatur der Flüssigkeit ist zu hoch Temperatur zu niedrig...
Page 41
Deutsch ANLAGE A1 Commissioning „Open loop cooling circuit“ Inbetriebsetzung “Rückkühler mit offenem Kreislauf” Canister H O + Glycol Kanister H O + Glykol 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 42
Deutsch Tools Werkzeuge Zeit – 30 Min. Time- 30 min. Application Anwendung Chiller OFF Rückkühler OFF O + Glycol O + Glykol 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 43
Deutsch ANLAGE B1 Wartung / Kontrollen und Inspektionen ACHTUNG! Vor jeder Wartungsarbeit, bei deren Ausführung die Maschine nicht in Betrieb sein muss, ist Stromversorgung unterbrechen neben Hauptschalter Schild „ACHTUNG WARTUNGSARBEITEN“ anzubringen. Die Ausführung des unten aufgeführten Test- und Kontrollprogramms trägt dazu bei, die Lebensdauer des Geräts zu verlängern und eventuellen Störungen vorzubeugen.
Page 44
Deutsch • Einmal im Monat kontrollieren, dass die Außenoberfläche des Kondensators sauber ist. Die Oberfläche der Kondensatorrippen darf keine Staubablagerungen, Produktrückstände oder Schlammablagerungen aufweisen. Picture 20 – Verflüssige Außenfläche für Picture 21 –Verflüssige Außenfläche für CCE 6101 – 6201 – 6301 CCE 6401 –...
Page 45
Deutsch ANLAGE B2 Elektrische und mechanische Komponenten Der Zugang zu den beiden Kreisläufen (Kühl- und Hydraulikkreislauf) erfolgt durch Abbau der Seitenplatten des Kühlgeräts Kompressor CCE 6101 – 6201 - 6301 Kompressor CCE 6401 – 6501 - 6601 Trocknungsfilter Fan Lüfter Druckwächter hoher Druck Druckwächter niederDruck Thermostatisches Ventil / Verdampfer...
Page 46
CCE Serie Standard CCE 6101 - CCE 6201 - CCE 6301 - CCE 6401 - CCE 6501 - CCE 6601 COSTRUTTORE DASSI S.r.l. – Member of the Pfannenberg Group Via La Bionda, 13 I-43036 Fidenza (PR) Tel. +39 0524-516711 Fax +39 0524-516790 E-mail: info@pfannenberg.it...
Page 47
Tel: +86-512 6287 1078 –Fax: +86-512 6287 1077 info@pfannenberg.cn - www.pfannenberg.cn Pfannenberg Asia Pacific Pte Ltd 61 Tai Seng Avenue # B1-01 UE Print Media Hub ASIA Singapore 534167 info@pfannenberg.com www.pfannenberg.com Per assistenza rivolgersi al centro Pfannenberg più vicino 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 48
Italiano Sommario Garanzia ................................... 49 Sicurezza ..................................49 Rischi residui ..................................51 Ricezione e disimballaggio............................... 52 Posizionamento del refrigeratore ............................52 Collegamenti ..................................53 Acqua / fluidi di processo ..............................55 8.1 Qualità dell’acqua................................56 Temperatura ambiente ..............................57 Messa in funzione del refrigeratore ..........................57 Messa fuori servizio e smaltimento ..........................
Page 49
Italiano 1. Garanzia Per le informazioni riguardanti la garanzia si prega di visitare il sito web Pfannenberg alla pagina: http://www.pfannenberg.com/it/azienda/condizioni-generali/ 2. Sicurezza L’installatore e il personale addetto all’esercizio del refrigeratore dovranno leggere le presenti istruzioni prima di mettere in funzione la macchina.
Page 50
Italiano Scollegare sempre l’alimentazione Folgorazione elettrica e durante gli interventi di assistenza collocare un cartello con la dicitura ‘MANUTENZIONE IN CORSO’ in posizione visibile accanto all’interruttore generale Scollegare sempre l’alimentazione Ventilatori rotanti elettrica e assicurarsi che tutte le apparecchiature meccaniche siano ferme prima di procedere con gli interventi di assistenza Si raccomanda l’utilizzo di dispositivi...
Page 51
Per assicurarsi che la performance del chiller non venga alterata, è raccomandato l’utilizzo di sole parti di ricambio originali acquistate da Pfannenberg. In questo modo verrà assicurata l’affidabilità e la qualità della macchina. In caso di necessità di informazioni aggiuntive riguardo ai pezzi di ricambio, per favore contattare il Servizio Assistenza Pfannenberg.
Page 52
Chiller. Evitare movimenti improvvisi che possono danneggiare il quadro e le componenti interne. PFANNENBERG Std Chiller (oltre i 45 Kg di peso) può essere fornito con 4 fori per il sollevamento e il trasporto;...
Page 53
0,3 m e 1,0 m al di sopra dell'altezza a cui si trovano i dispositivi per la manutenzione. I refrigeratori PFANNENBERG devono essere posizionati su una lastra di cemento che deve sporgere di almeno 30 cm oltre il perimetro del refrigeratore per evitare danni causati, per esempio, dalle attrezzature per la manutenzione del prato, ecc..
Page 54
• I refrigeratori Pfannenberg sono progettati per sistemi di messa a terra del tipo TN. Ai fini del dimensionamento in loco utilizzare il valore massimo di impedenza dell’anello di guasto del refrigeratore (vedere il valore Zpe specificato nello schema elettrico allegato).
Page 55
Italiano Limiti di voltaggio: In conformità alla norma CEI EN 60204-1 il funzionamento dei refrigeratori Pfannenberg standard è garantito entro i seguenti limiti: • Tensione nominale ± 10 % [V] • Frequenza nominale ± 1 % [Hz] Fare riferimento alla targhetta identificativa per verificare le condizioni operative nominali per l'unità.
Page 56
ATTENZIONE! I glicoli a base etilenica (Pfannenberg Protect PP…E) e a base propilenica (Pfannenberg Protect PP….P) differiscono in generale per la viscosità e la tossicità. Il glicole etilenico è meno viscoso di quello a base propilenica, pertanto in generale fornisce una maggiore efficienza nel trasferimento del calore, ed ha inoltre migliori prestazioni a basse temperature.
Page 57
Italiano Temperatura ambiente Il refrigeratore è progettato per funzionare nell'intervallo di temperatura ambiente indicato nell'etichetta macchina. Quando le temperature ambientali sono fuori di tale gamma, è necessario consultare il costruttore. Le alte temperature ambientali riducono la capacità di raffreddamento. Temperature basse richiedono controlli speciali, potrebbero essere necessari riscaldatori del fluido per impedirne il congelamento e per mantenere il fluido presente nel serbatoio del refrigeratore a una temperatura costante, così...
Page 58
Italiano • Realizzare il collegamento elettrico dell’alimentazione di corrente di rete e del cavo d’allarme con l’attrezzatura del cliente. Laddove i refrigeratori non sono forniti di cavi di alimentazione e allarmi (o dei connettori industriali), cablare in morsettiera, all’interno del quadro elettrico, in accordo allo schema elettrico allegato al refrigeratore. Figura 11 –...
Page 59
Gli interventi di calibrazione dei termostati, del pressostato o di qualsiasi altro componente del circuito di refrigerazione sono di competenza esclusiva del Servizio Assistenza Pfannenberg. Per maggiori informazioni relativamente all’installazione del refrigeratore, alla messa in funzione o alla risoluzione dei problemi contattare il Supporto Vendite Pfannenberg.
Page 60
• L'unità deve essere smaltita esclusivamente da personale autorizzato e qualificato. I rifiuti devono essere smaltiti correttamente anche da Pfannenberg. Le spese di spedizione per la consegna ad uno dei nostri stabilimenti di produzione devono essere pagate in anticipo.
Page 61
Italiano Tabella di localizzazione guasti Le informazioni riportate nel presente capitolo sono destinate al personale addetto all’assistenza e manutenzione. I guasti per i quali è necessario l’intervento di un tecnico frigorista possono essere gestiti solo da personale specializzato. Durante gli interventi sull’unità...
Page 62
Italiano Nota bene: dopo aver rimosso la causa del guasto, avviare il refrigeratore premendo il pulsante reset posizionato sul corpo esterno del pressostato (vedere figura) Compressore Problema Causa Possibile azione correttiva Il compressore resta costantemente in funzione e il refrigeratore non riesce a controllare la temperatura del liquido: temperatura del liquido troppo bassa temperatura del liquido troppo alta Temperatura troppo...
Page 63
Italiano ALLEGATO A1 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 64
Italiano Commissioning „Open loop cooling circuit“ Messa in funzione “Impianto di raffreddamento a circuito aperto” Canister H O + Glycol Tanica H O + Glicole Tools Attrezzi Tempo – 30 min. Time- 30 min. Application Applicazione Chiller OFF Refrigeratore OFF O + Glycol O + Glicole 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 65
Italiano ALLEGATO B1 Manutenzione / Controlli e ispezioni ATTENZIONE! Prima di qualsiasi intervento di manutenzione per il quale non è necessario che la macchina sia in funzione, scollegare l'alimentazione elettrica e posizionare il cartello “MANUTENZIONE IN CORSO” accanto all’interruttore generale lucchettabile in posizione “0” (Off). L’esecuzione del programma di test e controllo specificato sotto contribuirà...
Page 66
Italiano • Verificare che i valori di pressione, portata e temperatura del circuito idraulico rientrino nei limiti indicati sulla targhetta identificativa della macchina. • Se il refrigeratore è dotato di un filtro aria, esso deve essere sostituito/pulito una volta al mese o, se necessario, con una frequenza maggiore.
Page 67
Italiano ALLEGATO B2 Componenti elettrici e meccanici I circuiti frigorifero e idraulico sono accessibili rimuovendo i due pannelli laterali. Compressore CCE 6101 – 6201 - 6301 Condensatore CCE 6401 – 6501 - 6601 Filtro disidratatore Ventilatore Pressostato di alta pressione Pressostato di bassa pressione Valvola termostatica / Evaporatore Evaporatore...
Page 68
CCE Serie estándar CCE 6101 - CCE 6201 - CCE 6301 - CCE 6401 - CCE 6501 - CCE 6601 FABRICANTE DASSI S.r.l. – Member of the Pfannenberg Group Via La Bionda, 13 I-43036 Fidenza (PR) Tel. +39 0524-516711 Fax +39 0524-516790 E-mail: mail@pfannenberg.it...
Page 69
Tel: +86-512 6287 1078 –Fax: +86-512 6287 1077 info@pfannenberg.cn - www.pfannenberg.cn Pfannenberg Asia Pacific Pte Ltd 61 Tai Seng Avenue # B1-01 UE Print Media Hub ASIA Singapore 534167 info@pfannenberg.com www.pfannenberg.com Para solicitar el servicio de asistencia contacte con el centro Pfannenberg más cercano 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 70
ANEXO B1 ....................................87 ANEXO B2 ....................................89 1. Garantía Para información acerca de la garantía, por favor visite el sitio web Pfannenberg en la página: http://www.pfannenberg.com/it/azienda/condizioni-generali/ 2. Seguridad El instalador y el personal involucrado en el funcionamiento del refrigerador deben leer estas instrucciones antes de poner en funcionamiento la máquina.
Page 71
Español Riesgo Medida de seguridad recomendada Riesgo residual a tener en Adhesivo cuenta Aristas vivas (por ejemplo: Se recomienda usar los equipos de aletas del intercambiador protección (por ejemplo: guantes y de calor y esquinas de las prendas protectoras) placas metálicas interiores) Superficies calientes Se recomienda usar los equipos de (por ejemplo: cuerpo del...
Page 72
Español *NOTA: por razones medioambientales no descargue el refrigerante directamente en la atmósfera (respete las normas locales concernientes a la eliminación apropiada del refrigerante). Estudie detenidamente toda la documentación técnica suministrada con la unidad (por ejemplo: manual del regulador, diagramas mecánicos y eléctricos) para evitar un uso inapropiado del sistema. Es obligatorio respetar el Reglamento (UE) n°...
Page 73
Para asegurarse de que el desempeño de refrigerador no sea alterado, se recomienda utilizar solo piezas de repuesto originales compradas a Pfannenberg. De esta manera se asegura la fiabilidad y la calidad de la máquina. En caso de necesidad de información adicional acerca de las piezas de repuesto, contacte con el Servicio de Asistencia Pfannenberg.
Page 74
Evite movimientos bruscos que puedan dañar la estructura y los componentes internos. El enfriador estándar de PFANNENBERG (más de 45 kg de peso) puede incorporar 4 armellas para la elevación y transporte que se utilizarán para la carga/descarga vertical únicamente (para ver los puntos correctos de elevación, ver las etiquetas aplicadas en la unidad).
Page 75
0,3 m y 1,0 m por encima de la altura a la que están los dispositivos para el mantenimiento. Los refrigeradores Pfannenberg deben ser colocados en una losa de hormigón que debe sobresalir por lo menos 30 cm del perímetro del refrigerador para evitar posibles daños que puedan ser causados, por ejemplo, por los equipos de mantenimiento...
Page 76
• Los refrigeradores Pfannenberg están diseñados para sistemas de puesta a tierra de tipo TN. Para el dimensionamiento in situ, utilice el valor máximo de impedancia de bucle de defecto del refrigerador (véase valor Zpe especificado en el diagrama eléctrico adjunto).
Page 77
Español Límites de voltaje: De conformidad con la norma CEI EN 60204-1, el funcionamiento de los refrigeradores Pfannenberg está garantizado dentro de los siguientes límites: • Tensión nominal ± 10 %[V] • Frecuencia nominal ± 1 % [Hz] Consulte la placa de características para verificar las condiciones de funcionamiento nominales para la unidad.
Page 78
• Prevenga la contaminación biológica por mixobacterias y algas. Si esto se verificara, trate el agua con biocidas. PFANNENBERG recomienda comprobar las características del agua para determinar su calidad. Agua de calidad A (no requiere ningún tratamiento): Agua potable de red, exenta de contaminación Ph:7-9 Dureza: <5°dH...
Page 79
Español Puesta en funcionamiento del refrigerador ¡ATENCIÓN! LAS OPERACIONES EN LOS CIRCUITOS ELÉCTRICOS Y DE REFRIGERACIÓN PUEDEN SER LLEVADAS A CABO SOLO POR UN TÉCNICO CUALIFICADO. NOTA: A continuación se dan instrucciones detalladas acerca de las etapas de puesta en marcha. Para una guía rápida de puesta en marcha, véase anexo A1.
Page 80
Español • REFRIGERADOR con bomba: Coloque el interruptor general y el interruptor del circuito de la bomba (o bombas) en “on”. (el resto de los interruptores del circuito deben estar en “off”) Figura 12 – Interruptor de la bomba en ON •...
Page 81
Las operaciones de calibración de los termóstatos, del presóstato o de cualquier otro componente del circuito de refrigeración quedan bajo la responsabilidad exclusiva del Servicio de Asistencia de Pfannenberg. Para más información sobre la instalación del refrigerador, la puesta en marcha o la solución de problemas, póngase en contacto con PFANNENBERG 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 82
• La unidad debe ser eliminada exclusivamente por personal autorizado y calificado. Los residuos deben ser eliminados adecuadamente también por Pfannenberg. Los gastos de envío para la entrega a una de nuestras plantas de producción deben pagarse por adelantado.
Page 83
Español Tabla de búsqueda de averías La información contenida en este capítulo está destinada al personal encargado del servicio de asistencia y mantenimiento. Las averías que requieren el servicio de un técnico frigorista solo pueden ser reparadas por personal capacitado. Cuando se trabaja en la unidad hay que respetar todas las normas en materia de instalaciones eléctricas y las leyes vigentes en el país en el que está...
Page 84
Español • Asegúrese de que el refrigerador esté colocado en un lugar donde unidad de Temperatura ambiente refrigeración tenga una buena ventilación. excesiva También compruebe que la temperatura ambiente no supere el dato indicado en la etiqueta de la máquina •...
Page 85
Español ANEXO A1 Commissioning „Open loop cooling circuit“ Puesta en funcionamiento “Sistema de refrigeración de circuito abierto” 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 86
Español Canister H O + Glycol Bidón H O + Glicol Tools Herramientas Tiempo – 30 min. Time- 30 min. Application Aplicación Chiller OFF Refrigerador OFF Salida Entrada Máx. Mín. O + Glycol O + Glicol 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 87
Español ANEXO B1 Mantenimiento / Controles e inspecciones ¡ATENCIÓN! Antes de cualquier operación de mantenimiento para la que no es necesario que la máquina esté en funcionamiento, desconecte la alimentación eléctrica y coloque el cartel de “MANTENIMIENTO EN CURSO” al lado del interruptor general bloqueable con candado en posición “0”...
Page 88
Español • Si el refrigerador está equipado con un filtro de aire, habrá que sustituirlo/limpiarlo una vez al mes o, si es necesario, con una frecuencia mayor. • Una vez al mes, controle la parte exterior del condensador para asegurarse de que está limpio. En la superficie de las aletas del condensador no debe haber depósitos de polvo, productos residuales, ni lodos.
Page 89
Español ANEXO B2 Componentes eléctricos y mecánicos Para acceder a los dos circuitos (frigorífico e hidráulico) hay que quitar los paneles laterales del refrigerador. Compresor CCE 6101 – 6201 - 6301 Compresor CCE 6401 – 6501 – 6601 Filtro deshidratador Ventilador Presóstato de alta presión Presostato de baja presión...
Page 90
CCE Série standard CCE 6101 - CCE 6201 - CCE 6301 - CCE 6401 - CCE 6501 - CCE 6601 CONSTRUCTEUR DASSI S.r.l. – Member of the Pfannenberg Group Via La Bionda, 13 I-43036 Fidenza (PR) Tél. +39 0524-516711 Fax +39 0524-516790 E-mail: mail@pfannenberg.it...
Page 91
Tel: +86-512 6287 1078 –Fax: +86-512 6287 1077 info@pfannenberg.cn - www.pfannenberg.cn Pfannenberg Asia Pacific Pte Ltd 61 Tai Seng Avenue # B1-01 UE Print Media Hub ASIE Singapore 534167 info@pfannenberg.com www.pfannenberg.com Pour de l’assistance, s’adresser au centre Pfannenberg le plus proche. 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 92
ANNEXE A1..................................107 ANNEXE B1 ..................................109 1. Garantie Pour toute information concernant la garantie, veuillez consulter le site Internet de Pfannenberg à l'adresse suivante : http://www.pfannenberg.com/it/azienda/condizioni-generali/. 2. Sécurité L’installateur et le personnel préposé au fonctionnement de la centrale de refroidissement devront lire ces instructions avant la mise en service de la machine.
Page 93
Français Risque Mesure de sécurité recommandée Risque résiduel à prendre Adhésif en compte Il est recommandé d’utiliser des Arêtes vives (par exemple : ailettes de l’échangeur de dispositifs de protection (par exemple chaleur et arêtes des : gants et vêtements de protection). plaques métalliques internes).
Page 94
Français *NOTA BENE : pour des raisons de caractère environnemental, ne jamais décharger le réfrigérant directement dans l’atmosphère (s’en tenir aux dispositions locales concernant l’élimination correcte du réfrigérant). Étudier dans les détails toute la documentation technique fournie avec l’unité (par exemple : le mode d'emploi du régulateur, les schémas mécaniques et électriques) de manière à...
Page 95
Afin de garantir le parfait fonctionnement du refroidisseur, il est recommandé d'utiliser exclusivement des pièces de rechange d'origine vendues par Pfannenberg. Ceci permettra d'assurer la fiabilité et la qualité de la machine. Pour tout complément d'information concernant les pièces de rechange, veuillez consulter le Service Après-Vente Pfannenberg.
Page 96
équipé de fourches dont la longueur est supérieure à la base du Refroidisseur. Éviter tout mouvement brusque pouvant endommager la structure et les composants à l’intérieur. Le refroidisseur PFANNENBERG standard (dont le poids dépasse 45 kg) peut être fourni avec 4 œillets pour le levage et le transport ; à utiliser uniquement pour le chargement/déchargement vertical (pour voir le point correct pour le levage, veuillez vous référer aux autocollants sur l’unité).
Page 97
à une hauteur comprise entre 0,3 m et 1,0 m au-dessus de la hauteur où se trouvent les dispositifs pour l’entretien. Les centrales de refroidissement PFANNENBERG doivent être installées sur une dalle de béton qui doit dépasser d’au moins 30 cm le périmètre de la centrale de refroidissement pour éviter les dommages causés, par exemple, par les équipements pour l’entretien du pré, etc.
Page 98
électrique en annexe. • Les centrales de refroidissement Pfannenberg ont été conçues pour des systèmes de mise à la terre du type TN. Pour le dimensionnement sur place, utiliser la valeur maximum d’impédance de la boucle de défaut de la centrale de refroidissement (voir la valeur Zpe indiquée dans le schéma électrique en annexe).
Page 99
Français Limites de tension : Conformément à la norme CEI EN 60204-1, le fonctionnement des centrales de refroidissement Pfannenberg standards est garanti dans les limites suivantes : • Tension nominale ± 10 %[V] • Fréquence nominale ± 1 %[Hz] Se référer à la plaquette d’identification pour vérifier les conditions nominales et de fonctionnement de l’unité.
Page 100
Les glycols à base éthylénique (Pfannenberg Protect PP…E) et à base propylénique ATTENTION ! (Pfannenberg Protect PP….P) diffèrent généralement par leur viscosité et leur toxicité. Le glycol éthylénique étant moins visqueux que celui à base propylénique, il assure un meilleur transfert de la chaleur et il est en outre plus performant à...
Page 101
Français Température ambiante Le refroidisseur est conçu pour fonctionner dans la plage de température ambiante indiquée sur l’étiquette du type. Si les températures ambiantes sont hors de cette plage, veuillez consulter le fabricant. Les températures ambiantes élevées réduisent la capacité du refroidisseur. Les températures ambiantes basses requièrent des contrôles spéciaux. Des réchauffeurs de fluide peuvent être requis pour empêcher le gel et maintenir le fluide dans le réservoir du Refroidisseur à...
Page 102
Français • Réaliser le raccordement électrique de l’alimentation de courant de réseau et du câble d’alarme avec l’équipement du client. Lorsque les unités de refroidissement sont livrées sans câbles d'alimentation et sans alarmes (ou sans connecteurs industriels), il faut câbler le bornier, situé dans l'armoire électrique, selon le schéma électrique joint à la machine.
Page 103
Les interventions d’étalonnage des thermostats, du pressostat ou de tout autre composant du circuit de réfrigération relèvent exclusivement de la compétence du Service assistance Pfannenberg. Pour plus d’informations concernant l’installation de la centrale de refroidissement, la mise en service ou la résolution des problèmes, contacter PFANNENBERG.
Page 104
L’appareil ne doit être mis au rebut que par un personnel qualifié et autorisé. Les déchets doivent également être éliminés correctement par Pfannenberg. Les frais d’expédition pour la livraison à l’une de nos usines de fabrication doivent être payés à l’avance.
Page 105
Français Tableau de localisation des pannes Les informations figurant dans ce chapitre sont destinées au personnel préposé à l’assistance et à l’entretien. Les pannes pour lesquelles il est nécessaire qu’un technicien frigoriste intervienne peuvent être gérées uniquement par du personnel spécialisé. Durant les interventions sur l’unité, s’en tenir à...
Page 106
Français • Sens de rotation du Vérifier la connexion sur le bornier du boîtier électrique ; Contrôler la rotation ventilateur incorrect correcte du moteur électrique (uniquement version triphasée). • Vérifier que la centrale de refroidissement est installée dans un endroit Température ambiante assurant une ventilation adéquate de l’unité...
Page 107
Français ANNEXE A1 Commissioning „Open loop cooling circuit“ Mise en service « Système de refroidissement à 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 108
Français circuit ouvert » Canister H O + Glycol Bidon H O + Glycol Tools Outils Temps – 30 mn Time- 30 min. Application Application Chiller OFF Centrale de refroidissement OFF O + Glycol O + Glycol 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 109
Français ANNEXE B1 Entretien / Contrôles et inspections ATTENTION ! Avant d’effectuer toute intervention d’entretien pour laquelle il n’est pas nécessaire que la machine soit en marche, couper l’alimentation électrique et placer le panneau « ENTRETIEN EN COURS » près de l’interrupteur général verrouillable en position «...
Page 110
Français • Si la centrale de refroidissement est dotée d’un filtre à air, celui-ci devra être remplacé/nettoyé une fois par mois ou, au besoin, avec une plus grande fréquence. • Effectuer une fois par mois un contrôle de la partie externe du condenseur de manière à vérifier qu’elle est propre. La surface des ailettes du condenseur ne doit pas présenter de dépôts de poussière, de résidus de produits ou de boues.
Page 111
Français ANNEXE B2 Composants électriques et mécaniques Les circuits de refroidissement et hydraulique sont accessibles en enlevant les deux panneaux latéraux. Compresseur CCE 6101 – 6201 - 6301 Compresseur CCE 6401 – 6501 - 6601 Filtre déshydrateur Ventilateur Pressostat haute pression Condenseur Vanne thermostatique Évaporateur...
Page 112
CCE 6101 CCE 6201 CCE 6301 CCE 6401 CCE 6501 CCE 6601 ИЗГОТОВИТЕЛЬ DASSI S.r.l. – Member of the Pfannenberg Group Via La Bionda, 13 I-43036 Fidenza (PR) Tel. +39 0524-516711 Fax. +39 0524-516790 E-mail: mail@pfannenberg.it Русский Инструкция по эксплуатации...
Page 113
Tel: +86-512 6287 1078 –Fax: +86-512 6287 1077 info@pfannenberg.cn - www.pfannenberg.cn Pfannenberg Asia Pacific Pte Ltd 61 Tai Seng Avenue # B1-01 UE Print Media Hub АЗИЯ Singapore 534167 info@pfannenberg.com www.pfannenberg.com Для обслуживания обращайтесь в ближайший к вам центр Pfannenberg. 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 114
ПРИЛОЖЕНИЕ A1 ................................129 ПРИЛОЖЕНИЕ B1 ................................131 ПРИЛОЖЕНИЕ B2 ................................133 1. Гарантия Более подробная информация по гарантии представлена на сайте компании Pfannenberg: http://www.pfannenberg.com/it/azienda/condizioni-generali/ 2. Безопасность Монтажник и персонал, ответственный за функционирование чиллера, должны прочитать данные инструкции перед тем, как приводить агрегат в действие.
Page 115
Русский В целях охраны здоровья и безопасности далее приведен перечень возможных рисков, которым подвергается оператор во время запуска в работу, и/или функционирования, и/или демонтажа агрегата: Риск Рекомендованная мера Остаточный Наклейка безопасности риск, который необходимо учитывать Острые углы (например: Рекомендуется использование лопасти...
Page 116
Русский *ПРИМЕЧАНИЕ: по экологическим причинам никогда не выпускайте хладагент в атмосферу (соблюдайте местные нормативные документы по правильному выбросу хладагентов). Внимательно изучите всю техническую документацию, которая поставляется вместе с оборудованием (например, руководство регулятора) чтобы избежать использования установки в недозволенных целях. Необходимо соблюдать Регламент (ЕС) n. 517/2014 Европейского парламента и Совета Европейского Союза от 16 апреля...
Page 117
компетентным властям государства-члена Европейского Союза, в котором используется установка. Чтобы обеспечить производительность чиллера во времени, рекомендуется использовать только оригинальные запасные части от компании Pfannenberg. Таким образом будет обеспечена надежность и качество работы агрегата. Если вы хотите получить более подробную информацию по запчастям, свяжитесь с отделом обслуживания клиентов...
Page 118
грузоподъемностью и длиной вил, превышающей длину основания чиллера. Избегайте резких движений, которые могут повредить структуру оборудования и его внутренние компоненты. Стандартный чиллер производства компании PFANNENBERG (вес выше 45 кг) может быть поставлен с 4 рымболтами для подъема и перемещения оборудования. Используйте их исключительно для вертикальной погрузки/разгрузки (для определения правильных подъемных точек...
Page 119
Для облегчения проведения операций по обслуживанию и настройке чиллер должен располагаться между 0,3 м и 1,0 м над уровнем обслуживания. Чиллеры PFANNENBERG устанавливаются на бетонной плите, которая должна выходить за периметр чиллера не менее 30 см чтобы избежать поломок от, например, газонного оборудования и т.д. Чиллер должен быть расположен на...
Page 120
Проверьте, чтобы напряжение и частота электропитания соответствовало указанным на идентификационной табличке агрегата и/или прилагаемой электросхеме. • Чиллеры Pfannenberg разработаны для систем заземления типа TN. Для определения размеров на месте используйте максимальное значение сопротивления неисправного контура чиллера (см. значение Zpe, указанное в прилагаемой электросхеме).
Page 121
Для агрегатов с нестандартным напряжением проверяйте значение на этикетке машины. Вода / технологические жидкости Чиллеры PFANNENBERG должны быть заполнены до нужного уровня специальным ингбированным гликолем для промышленных охладительных установок. Не используйте антифриз для автомобилей. Ингибиторы, которые используются в антифризах для автомобилей, могут быстро разлагаться и ускорять ухудшение основы хладагента...
Page 122
ВНИМАНИЕ! Гликоль на основе этилена (Pfannenberg Protect PP…E) и на основе пропилена f(Pfannenberg Protec PP….P) обычно различаются по вязкости и токсичности. Гликоль на основе этилена менее вязкий по сравнению с гликолем на основе пропилена, поэтому обычно более эффективен при передаче тепла и, кроме того, дает лучшие результаты при низких температурах.
Page 123
Русский Температура окружающей среды Чиллер предназначен для работы в температурном диапазоне, который указан на табличке оборудования. Если температура окружающей среды выходит за указанные пределы, необходимо обратиться к изготовителю за консультацией. Высокая температура окружающей среды снижает производственные характеристики чиллера. Низкая температура требует особых проверок. Может потребоваться нагрев жидким теплоносителем чтобы избежать замерзания...
Page 124
Русский • Выполните электрическое подключение сетевого питания и аварийный кабель к оборудованию заказчика. Если чиллеры поставлены без силового кабеля и аварийной системы (или без промышленных подсоединений), провести проводку к клеммнику внутри электрощита согласно поставленной вместе с чиллером электросхеме. Рис. 11– Эл.подключение •...
Page 125
После завершение установки ЧИЛЛЕР не нуждается в управлении специализированным оператором. Настройка термостатов, реле давление или других компонентов охладительного контура должны выполняться исключительно отделом обслуживания или техническим специалистом по обслуживанию Oтделa Tехпомощи Pfannenberg. Для более подробной информации по установке чиллера, вводу в эксплуатацию или по устранению проблем...
Page 126
Хладагент выкачивают и перерабатывают на специализированных предприятиях. Не сливайте хладагент в окружающую среду. • Утилизация устройства поручается специализированному персоналу соответствующей квалификации. Отходы следует перерабатывать согласно правилам в т. ч. на Pfannenberg. Расходы по транспортированию до одного из наших производственных предприятий должны быть оплачены заранее. 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 127
Русский Таблица обнаружения неисправностей Информация настоящей главы предназначена для персонала, ответственного за обслуживание и ремонт. Неполадки, для устранения которых необходим специалист по холодильному оборудованию, могут устраняться только специализированным персоналом. Во время обслуживания системы соблюдайте все правила по технике безопасности для работы на электроустановках и нормы, которые действуют в стране функционирования установки. Чиллер...
Page 128
Русский температура окружающей Проверьте, чтобы температура окружающей среды не была выше среды значения, указанного на этикетке машины. • Установите боковые стенки. Охладитель запущен при неустановленных боковых стенках Примечание: после того, как будет устранена причина неисправности, запустить чиллер, нажав кнопку сброса, расположенную...
Page 129
Русский ПРИЛОЖЕНИЕ A1 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...
Page 130
Русский Commissioning „Open loop cooling circuit“ Ввод в эксплуатацию «Холодильная установка с открытым контуром» Канистра H2O + Гликоль Canister H O + Glycol Инструменты Tools Время- 30 мин. Time- 30 min. Применение Application Чиллер ВЫКЛ Chiller OFF Выкл Вкл Макс Мин...
Page 131
Русский ПРИЛОЖЕНИЕ B1 Техническое обслуживание / Проверки и инспекции ВНИМАНИЕ! Перед выполнением обслуживания, для которого машина не должна быть включенной, обесточьте агрегат и установите табличку «ИДЕТ ОБСЛУЖИВАНИЕ» рядом с главным выключателем с висячим замком в положение “0” (Выкл). Выполнение программы испытаний и проверок, описанной далее, позволит продлить срок службы агрегата и защитить его...
Page 132
Русский • Если чиллер снабжен воздушным фильтром, то его нужно заменять/чистить раз в месяц или, если необходимо, чаще. • Раз в месяц проверять, чтобы внешняя поверхность конденсатора была чистой. Поверхность лопастей конденсатора не должна иметь отложений пыли, грязи или остатков продукции. Рис.
Page 133
Русский ПРИЛОЖЕНИЕ B2 Электрические и механические компоненты Для доступа к охладительному и гидравлическому контурам снимите боковые панели. Компрессор CCE 6101 – 6201 - 6301 Компрессор CCE 6401 – 6501 - 6601 Фильтр-осушитель Реле высокого давления Реле низкого давления Термостат Испаритель Насос...
Page 134
Русский OCUMENT REVISION HISTORY Date Revision Description Name 29/08/2017 01-_ First Release 27/12/2021 01-A Added Weee regulation 70040-170_01-A(CCE_Op._Manual_EN-DE-IT-ES-FR-RU).docx...