TECHNICAL FEATURES
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
For use on hot air generator the burner must be fitted with control box type 479SE or 539SE.
Burner with CE marking in conformity with EEC directives: EMC89/336/EEC, Low Voltage 73/23/EEC,
Machines 98/37/EEC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529.
CE Certification No. : 0036 0257 as 92/42/EEC.
8
4
3
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Screws fixing air-damper
7 – Hydraulic jack with air-damper
8 – Lock-out lamp and reset button
9 – Flange with insulating gasket
10 – Combustion head adjustment screw
1554
G10
CODE
54 – 120 kW
Gas oil, max. viscosity at 20 ° C: 6 mm
Single phase, 230 V ± 10%
Run current 0.80 A – 2850 rpm – 298 rad/s
4 m F
Secondary 8 kV – 16 mA
Pressure 7 – 15 bar
0.170 kW
D5668
3746411
–
4.5 – 10 kg/h
~
Fig. 1
7
6
6
9
EQUIPMENT
Quantity
2
Flexible pipes with nipples
1
Flange with insulating gasket
4
Screws and nuts for flange
1
Hinge
1
Screw with two nuts for flange
1
GB
464T1
TYPE
/s (1.5 ° E)
2
50Hz
10
2
1
Description
5