Forced draught gas burner
TECHNICAL FEATURES
Thermal output
Net heat value
Gas
(Family 2)
Pressure
Electrical supply
Motor
Capacitor
Ignition transformer
Absorbed electrical power
For gas family 3 (LPG) ask for separate kit.
COUNTRY
GAS CATEGORY
CE marking according to Gas Appliance Directive 90/396/EEC; PIN 0063AP6680.
According to directives: EMC 89/336/EEC, Low Voltage 73/23/EEC, Machines 98/37/EEC and
Efficiency 92/42/EEC.
Gas train according to EN 676.
1 – Air-damper
2 – Screws for fixing the air-damper
3 – 7 pole socket for electrical supply
and control
4 – 6 pole socket for gas train
5 – Grommet
6 – Screw for fixing the cover
7 – Lock-out lamp and reset button
NOTES
– The grommet (5) supplied with the burner, must be fitted to the same side of the gas train.
– After having installed the burner verify the access to the fixing screws of the cover.
If necessary replace them with the fixing screws (6) fig. 1 supplied as equipment.
2056
FS20
81 – 218 kW
8 – 12 kWh/m
min. 20 mbar
single phase, 230 V ± 10%
230 V / 1.4 A
5 µ F
primary 230 V / 1.8 A – secondary 8 kV / 30 mA
0.25 kW
FR
GB - IE
II2Er3P
II2H3P
3756931
CODE
–
69,700 – 187,500 kcal/h
3
– 7,000 – 10,340 kcal/m
– max. 35 mbar
DK - AT - GR - SE
II2H3B/P
II2ELL3B/P
7
6
5
1
GB
569T30
TYPE
3
~
50Hz
DE
LU
II2E3B/P
Fig. 1
4
3
D5260
NL
II2L3B/P
1
2
2