Commissioning; Commissioning Checklist; Learning Mode; Use - PLYMOVENT controlGo Manuel D'installation Et D'utilisation

Masquer les pouces Voir aussi pour controlGo:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

5

coMMiSSioNiNG

5.1
General
Make sure that the Panel is connected to the mains.
Turn the main switch (refer to Fig. 6.1E) on.
5.2

Commissioning checklist

#
Check
1.
Is the addressing sequence of the filter
modules correct?
Extraction fan
2.
Push the START/STOP FAN button (ref.
Fig. 6.1F) to start the fan.
Push the button again to stop the fan.
Filter cleaning system
3.
MDB only:
Push the FILTER CLEANING button (ref.
Fig. 6.1G) to activate the filter cleaning
system.
If applicable: apply precoat material to
the filter cartridges; refer to the MDB
manual.
Push and hold the START/STOP FAN
button for 20 seconds to activate the
precoat timer. Feedback: the green LED
blinks 4 times and the buzzer sounds
shortly.
SCS only:
Do not test this function to maintain the
protective layer of precoat.
Plymovent VFD/Panel (frequency inverter) (option)
4.
Have you changed the parameter set
(PT-1000) or 2 (PT-2500)? Refer to the
instruction sheet supplied with the VFD/Panel.
Default setting = 3 / ControlPro
*)
If any problems or errors occurs, refer to chapter 8 /
Troubleshooting.
5.3

Learning Mode

The Learning Mode is only applicable for MDB systems and
systems with two connected SCS systems (master/slave).
attENtioN
ControlGo Panels are factory-wise prepared for use
with either MDB or SCS / EDS filter systems. They
are not interchangeable.
In case of:
- one SCS system; or
- EDS (Diluter) systems
proceed with chapter 6.
In the Learning Mode you "teach" the Panel about the size of
the filter system;
- MDB: the number of filter cartridges (min. 2, max. 64)
- SCS: the number of filter systems (1 or 2; default setting: 1)
At the same time, the Learning Mode verifies the cable
connections of the SlaveBoard(s) and the correct setting of the
DIP switches.
WaRNiNG
You must go through the Learning Mode procedure
to make sure that all SlaveBoards of the filter
modules are correctly connected. If you fail to do
so, it can finally lead to a malfunction of the filter
cleaning system.
0000112607/170717/0 ControlGo
Ref.
oK
par.
4.4.4
into 1
1.3.1
*)
5.3.1
General
Follow the flowchart GENERAL on page 79.
Explanatory notes:
A
Leave the Panel open.
B
Push and hold the black button. Turn the main
switch on at the same time. Continue to hold the
button; the white LED shows a "heartbeat"
blinking pattern (Learning Mode is starting up).
C
When the green and red LEDs are on and the
white LED is blinking, release the black button
(Learning Mode is initializing).
D Wait until the white LED is on. The Learning
Mode is activated now.
In case of an MDB system:
Proceed with paragraph 5.3.2
In case of two SCS systems:
Proceed paragraph 5.3.3
5.3.2
MDB
Follow the flowchart MDB on page 80.
Explanatory notes:
A
Count the number of flashes of the yellow LED in
one blinking cycle (min. 2, max. 64). Interval
between two blinking cycles: 5 seconds.
B
Make sure that the number of flashes
corresponds with the number of filter
cartridges...
C
If NOT and the buzzer sounds, no filter
cartridges are detected at all. Push the black
button during ≥5 seconds to suppress the
buzzer.
D Make sure that all cables and connections to the
SlaveBoard(s) are correctly installed.
E
Make sure that all DIP switches are correctly
addressed (refer to Fig. 4.12 and Fig. 4.13).
F
Push the black buttton shortly to restart the
Learning Mode. Repeat step A and onwards.
5.3.3
SCS (two filter systems)
Follow the flowchart SCS (#2) on page 81.
Explanatory notes:
A
By default, the yellow LED blinks one time, with
an interval of 5 seconds.
B
Push the green button to change the setting
from 1 to 2 filter systems. This is indicated by
the yellow LED that flashes two times.
6

USE

6.1

Control panel

The control panel contains the following controls and
indicators:
Fig. 6.1 (also refer to Fig. V on page 76)
A
White LED | POWER ON
- LED off: system is off
- LED blinking: system is starting up
- LED on: system is ready
EN - 12

Publicité

Table des Matières
loading

Table des Matières