Adjustment For High Altitude; Adjustment For Vent Length (Indoor Models Only); Checklist For Gas And Electricity - Rinnai RUR98i Manuel D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Adjustment for High Altitude

Set SW2 and SW3 in DIPSW 1 to the values shown in
table below for your altitude. The default setting for
the appliance is 0-2000 ft (0-610 m) with switches
SW2 and SW3 in the OFF position.
When the DIP switch is adjusted, it is not necessary to
adjust the gas pressure setting for high altitude.
Altitude
0-2000 ft (0-610 m)
2001-5200 ft (610-1585 m)
5201-7700 ft (1585-2347 m)
7701-10200 ft (2347-3109 m)
Adjustment for Vent Length
(indoor models only)
Adjust SW 1 in DIPSW 1 if required. Refer to the
section "Maximum vent length".
SW 2 in
SW 3 in
DIPSW 1
DIPSW1
OFF
OFF
OFF
ON
ON
OFF
ON
ON
KBP Series Manual

Checklist for Gas and Electricity

A manual gas control valve is placed in the gas
line to the water heater.
Check the gas lines and connections for leaks.
Confirm that the gas inlet pressure is within
limits.
Confirm that the water heater is rated for the gas
type supplied.
Confirm that the electricity is supplied from 120
VAC, 60 Hz power source and is in a properly
grounded circuit.
Confirm that an extension cord or an adapter plug
has NOT been used with the water heater.
49

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Rur98eReu-kbp3237ffud-usReu-kbp3237wd-us

Table des Matières