Service Menu; Configuration Menu - Lamborghini Caloreclima TAURA D 24 MCS Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

A - Upstream pressure point
B - Downstream pressure point
R
I - Gas valve electrical connection
R - Gas outlet
B
S - Gas inlet
I
A
TYPE SGV100
Pi max 65 mbar
24 Vdc - class B+A
S
fig. 15 - Gas valve
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons detail 3 - fig. 1 to increase or decrease the power (min. = 00 - max. =
100). Press the reset button within 5 seconds and the max. power will remain that just
set. Exit TEST mode (see sec. 4.1).

Configuration Menu

Press the DHW buttons together for 10 seconds to access the configuration Menu. 7 pa-
rameters indicated by the letter "b" are available: which are not modifiable from Remote
Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to modify the value of a parameter: the change will be au-
tomatically saved.
Con-
Description
tents
b01
Gas type selection
b02
Boiler type selection
b03
Combustion chamber type selection
Primary Exchanger type selection
(b03=0)
No effect on adjustment (b03=1)
b04
No effect on adjustment (b03=2)
Primary Exchanger type selection
(b03=3)
Relay card LC32
operation selection (b02=1)
b05
No effect on adjustment (b02=2)
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
b06
Mains Voltage Frequency
Comfort burner on time
(b02=1)
No effect on adjustment (b02=2)
b07
No effect on adjustment (b02=3)
No effect on adjustment (b02=4)
26
EN
~ 24Ω
fig. 16 - Gas valve connection
Range
Default
0=Natural Gas
0=Natural Gas
1=LPG
1=Bithermal instantaneous
2=Monothermal instantaneous
1=Bithermal instanta-
neous
3=Heating only (3-way valve)
4=Heating only (circulating pump)
0=Sealed Chamber combustion control
(without fume pressure switch)
1=Open Chamber (with fume thermostat)
0=Sealed Chamber
with
2=Sealed Chamber (with fume pressure
combustion control
switch)
3=Sealed Chamber combustion control
(with fume thermostat on recuperator)
0=Flat
1=Omega
0=Flat
2=--
--
0
--
0
0=Flat
1=Omega
0=Flat
2=--
0=External gas valve
1=System filling solenoid valve
0=External gas valve
2=Solar 3-way
--
0
--
0
--
0
0=50Hz
0=50Hz
1=60Hz
0-20 seconds
5 seconds
--
5
--
5
--
5
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.

Service Menu

Press the Reset button for 20 seconds to access the card Service Menu. 4 submenus
are available: press the Heating buttons to select , in increasing or decreasing order, "tS",
"In", "Hi" or "rE". tS" means Transparent Parameters Menu, "In" Information Menu, "Hi"
~ 65Ω
History Menu: after selecting the submenu, press the Reset button again to access it ;
"rE" means History Menu Reset: see description
"tS" - Transparent Parameters Menu
16 parameters indicated by the letter "P" are available: which are also modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to display or modify the value of a parameter: the change
will be automatically saved.
Con-
Description
tents
P01
Ignition ramp Offset
P02
Heating ramp
P03
Heating standby time
P04
Heating Post-Circulation
P05
Heating user max. set point
P06
Max. heating power
Burner shutdown in hot water production (b02=1)
P07
Burner shutdown in hot water production (b02=2)
Hot water tank hysteresis (b02=3)
Hot water tank hysteresis (b02=4)
DHW standby time (b02=1)
DHW standby time (b02=2)
P08
DHW standby time (b02=3)
DHW standby time (b02=4)
DHW user max. set point (b02=1)
DHW user max. set point (b02=2)
P09
DHW user max. set point (b02=3)
DHW user max. set point (b02=4)
Anti-inertia function temperature (b02=1)
No effect on adjustment (b02=2)
P10
Delivery temperature in hot water production (b02=3)
Delivery temperature in hot water production (b02=4)
Anti-inertia function Post-Circulation (b02=1)
DHW Post-Circulation (b02=2)
P11
DHW Post-Circulation (b02=3)
DHW Post-Circulation (b02=4)
P12
DHW max. power
P13
Absolute min. power
P14
Post-Ventilation
CO2 limit Offset (b03=0)
No effect on adjustment (b03=1)
P15
No effect on adjustment (b03=2)
CO2 limit Offset (b03=3)
P16
Exchanger protection activation
cod. 3541A220 - 01/2011 (Rev. 00)
TAURA D MCS
Range
Default
0-40
10
1-20°C/minute
5°C/minute
0-10 minutes
2 minutes
0-20 minutes
6 minutes
31-85°C
85°C
0-100%
100%
0=Fixed
1=Linked to set point
2=Solar (5)
0=Fixed
3=Solar (10)
4=Solar (20)
0=Fixed
1=Linked to set point
2=Solar (5)
0=Fixed
3=Solar (10)
4=Solar (20)
0-4°C
2°C
0-4°C
2°C
0-60 seconds
30 seconds
0-60 seconds
60 seconds
0-60 seconds
30 seconds
0-60 seconds
30 seconds
50-65°C
50°C
50-65°C
55°C
50-65°C
65°C
50-65°C
65°C
70-85°C
70°C
--
0
70-85°C
80°C
70-85°C
80°C
0-5 Seconds
0 seconds
0-60 Seconds
30 seconds
0-60 Seconds
30 seconds
0-60 Seconds
30 seconds
0-100%
100%
0-100%
0%
0=Default
0=Default
1=50 seconds
0 (Minimum)
20
30 (Maximum)
--
20
--
20
0 (Minimum)
20
30 (Maximum)
0=No F43
10°C/second
1-15=1-15°C/second

Publicité