Commissioning
Parameter setting with the XT EMZ9371BC keypad
V/f characteristic control
Parameter setting with the XT EMZ9371BC keypad
,
Read the documentation for the keypad before starting work!
)
Note!
In the "Diagnostic" menu you can monitor the most important drive parameters
V/f characteristic control
The following instructions apply to controllers equipped with a standard−I/O function module and
a three−phase AC motor which has been selected according to a power−based assignment.
Switch−on sequence
1.
Plug in the keypad
2.
Ensure that controller inhibit is active after mains
connection
3.
Switch on the mains
4.
After approx. 3 s the keypad is in the operating level and
displays the output frequency (C0050) and the device
utilisation (C0056)
5.
For quick commissioning you select the "Quick start"
menu
Change the menu level with V
A
B
Change to the "Quick start" menu and from there to the
submenu "V/f quick" with z z Z z
Change to the code level with Z to parameterise your
C
drive
6.
Adapt the voltage/current range for the analog setpoint
selection (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
7.
If required, adapt the fixed setpoints JOG.
A
JOG 1 (C0037)
Lenze setting: 20 Hz
B
JOG 2 (C0038)
Lenze setting: 30 Hz
C
JOG 3 (C0039)
Lenze setting: 40 Hz
140
Comment
Terminal X3/28 = LOW
The submenu "V/f quick" contains the codes
which you require for commissioning a standard
application. The digital inputs are configured in
the Lenze setting:
X3/E1, X3/E2: activation of fixed setpoints (JOG)
X3/E3: activation of DC injection brake (DCB)
X3/E4: CW rotation/CCW rotation
Set the DIP switch on the standard I/O to the
same range (see Mounting Instructions for the
standard I/O)
Activation:
X3/E1 = HIGH, X3/E2 = LOW
Activation:
X3/E1 = LOW, X3/E2 = HIGH
Activation:
X3/E1 = HIGH, X3/E2 = HIGH
l