Troubleshooting and fault elimination
Fault elimination
Fault messages
Fault messages
1)
Keypad
PC
Fault
0
No fault
noer
71
System fault
ccr
a
61
Communication
ce0
error on AIF
a
(configurable in
C0126)
62
Communication
ce1
error on CAN−IN1
a
with sync control
63
Communication
ce2
error on CAN−IN2
a
64
Communication
ce3
error on CAN−IN1
a
with event or time
control
65
BUS−OFF
ce4
(many
a
communication
errors occurred)
66
CAN time−out
ce5
(configurable in
a
C0126)
158
Cause
−
Strong interference injections on
the control cables
Earth loops in the wiring
Faulty transmission of control
commands via AIF
CAN−IN1 object receives faulty
data, or communication is
interrupted
CAN−IN2 object receives faulty
data, or communication is
interrupted
CAN−IN1 object receives faulty
data, or communication is
interrupted
Controller has received too many
faulty telegrams via the system
bus and has been disconnected
from the bus
For remote parameterisation via
the system bus (C0370):
Slave does not respond.
Communication monitoring time
has been exceeded
For operation with application
I/O:
Parameter set change−over has
been parameterised incorrectly
For operation with module on
FIF:
Internal error
l
Remedy
−
Shield control cables
Insert the communication module
firmly into the diagnosis terminal
l
Check plug connection bus
module ó FIF
l
Check transmitter
l
Increase monitoring time in
C0357/1, if necessary
l
Check plug connection bus
module ó FIF
l
Check transmitter
l
Increase monitoring time in
C0357/2, if necessary
l
Check plug connection bus
module ó FIF
l
Check transmitter
l
Increase monitoring time in
C0357/3, if necessary
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
l
Check wiring of the system bus
l
Check system bus configuration
The "parameter set change−over"
signal (C0410/13, C0410/14) must be
connected to the same source in all
parameter sets
Contact Lenze