Warnings!
Motor Overload Protection
ƒ
For information on the protection level of the internal overload protection for a
–
motor load, see the corresponding manuals or software helps.
If the integral solid state motor overload protection is not used, external or
–
remote overload protection must be provided.
Branch Circuit Protection
ƒ
The integral solid state protection does not provide branch circuit protection.
–
Branch circuit protection has to be provided externally in accordance with
–
corresponding instructions, the National Electrical Code and any additional codes.
Please observe the specifications for fuses and screw−tightening torques in these
ƒ
instructions.
E82xV251K2C ... E82xV222K2C (0.25 kW ... 2.2 kW, 240 V devices):
ƒ
Suitable for use on a circuit capable of delivering not more than 5000 rms
–
symmetrical amperes, 240 V maximum, when protected by fuses or circuit
breakers.
Suitable for use on a circuit capable of delivering not more than 50000 rms
–
symmetrical amperes, 240 V maximum, when protected by CC, J, T or R class
fuses.
Shall be installed in a Pollution Degree 2 macro−environment.
–
Maximum surrounding air temperature: 0 ... +55 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.
–
E82xV551K4C ... E82xV222K4C (0.55 kW ... 2.2 kW, 400/500 V devices):
ƒ
Suitable for use on a circuit capable of delivering not more than 5000 rms
–
symmetrical amperes, 500 V maximum, when protected by fuses or circuit
breakers.
Suitable for use on a circuit capable of delivering not more than 50000 rms
–
symmetrical amperes, 500 V maximum, when protected by CC, J, T or R class
fuses.
Shall be installed in a Pollution Degree 2 macro−environment.
–
Maximum surrounding air temperature: 0 ... +55 °C
–
> +40 °C: reduce the rated output current by 2.5 %/°C
–
Use 60/75 °C or 75 °C copper wire only.
–