1)
Keypad
PC
Fault
67
System bus (CAN)
ce6
function module on
a
FIF has the
"Warning" or
"BUS−OFF" status
(configurable in
C0126)
68
Communication
ce7
error during remote
a
parameterisation
via system bus
(C0370)
(configurable in
C0126)
91
External fault
EEr
(TRIP−SET)
a
−
Communication
ErP0
abort between
...
keypad and
standard device
ErP19
a
Fan failure
95
FAn1
(only 8200 motec
a
3 ... 7.5 kW)
TRIP or warning
−
FAn1
configurable in
C0608
105
Internal fault
H05
a
140
Faulty parameter
id1
identification
a
32
Motor phase error
LP1
(display when
a
C0597 = 1)
182
Motor phase error
LP1
(Display when
C0597 = 2)
EDK82EV222 DE/EN/FR 13.0
Troubleshooting and fault elimination
Cause
CAN controller reports "Warning"
or "BUS−OFF" status
Node does not respond or is not
available
For operation with application
I/O:
Parameter set change−over has
been parameterised incorrectly
A digital signal assigned to the
TRIP−Set function is activated
Various
Fan is defective
Fan is not connected
Motor is not connected
l
Failure of one/several motor
phases
l
Motor current is too low
l
Fault elimination
Fault messages
Remedy
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
The "parameter set change−over"
signal (C0410/13, C0410/14) must be
connected to the same source in all
paramerter sets
Check external encoder
Contact Lenze
Replace fan
Connect fan
Check wiring
Contact Lenze
Connect motor
l
Check motor supply cables
l
Check V
boost,
min
l
Connect motor with a
corresponding power or adapt
motor with C0599
8
159