sigfox MODBUS MASTER - Guide utilisateur / User guide version V1.0.0

3.4. Description of the registers

On switching on the product works according to the last saved configuration (Factory Configuration if it is the first start, or if this configuration
has not been changed).
Commands such as Modification TTY<n>=<M> or ATR allow you to change the content of the registers: <n> repre-senting the number of the
register and <m> the value to be assigned. This latter is either a decimal value or a hexadecimal value consistent with the «encoding» column
FR
of the tables below.
Examples:
• ATS300=6 assigns the decimal value 6 in register 300
• ATS320=2 assigns the hexadecimal value 0x02 in register 302
It is imperative to save the parameters with the command AT&W before exiting the Command mode otherwise all changes will be lost.
EN
IMPORTANT: The registers that are not documented (that can appear in the list following the AT/S command) in
the paragraphs that follow are reserved and must not be changed.

3.4.1 Function registers

The list of registers below allows you to change the behaviour of the product application.
Register
Size
(bytes)
300
1
301
2
304
2
306
1
307
2
320
2
Description
Coding
Transmission period of
Decimal
the Keep Alive frame
Transmission period of
Decimal
data sensors
PIN code
Decimal
Global operation
Decimal
Number of downling
Decimal
frame per day
Data acquisition period
Decimal
for alarm
Details
Default: 144
Min/max: 1 à 255
Unit:
x 10min if S306=1
x 20s if S306=2
Default: 4320
Min/max : 1 to 4320
Unit: x 20 seconds
The value 4320 is equivalent to a period of 24 hours.
Default : 0 (disabled)
Min/max : 0 to 9999
PIN code used with ATPIN command.
Value 0 disables the PIN code.
Default: 0
Allows the product to be switched into one of the following modes:
• 0: PARK mode
• 1: Production mode
• 2: TEST mode
Default: 0
Min/Max: 0 to 4
Unit: none
See detail paragraph 4.2
Default: 4320
Min/max : 1 to 4320
Unit: x 20 seconds
The value 4320 is equivalent to a period of 24 hours.