Contakt arrangements
Ex 23 / Ex28 / Ex 29 switch
Switch mechanism
4
5
Special switch
mechanism
7
8
40
Explosion-protected distributions GHG 619
1.26
Ex 28 control switch
Circuitry
Code
EC type examination certificate:
Rated voltage
Rated current:
6011
Switching capacity AC 15:
Switching capacity DC 13:
Perm. short-circuit back-up fuse:
6019
With gold-tipped contact:
Connection terminals:
Weight:
6060
1.27
Ex 29 control switch
6062
EC type examination certificate:
Rated voltage
6065
Max. Rated current:
Switching capacity AC 15:
Switching capacity DC 13:
6033
Perm. short-circuit back-up fuse:
With gold-tipped contact:
Connection terminals:
6170
Weight:
. 021
. 023
. 024
. 061
. 063
. 066
. 067
. 049
. 037
. 191
6
9
EATON's Crouse-Hinds Business
BVS 14 ATEX E 076 U
up to max. 500 V
max. 20 A (up > 12 A wiring >=2,5 mm²)
230 V / 8 A
400 V / 6,0 A
24 V / 6 A
230 V / 0,4 A
25 A gL bei 500 V
max. 400 mA
2x 0,5 - 4,0 mm² 1 x 1,0 - 6,0 mm²
1 level
2 levels
approx. 0.25 kg approx. 0.40 kg
BVS ATEX E 119 U
up to max. 500 V
16 A*
* (rated current > 12 A – terminal cross section >2.5mm²))
230 V / 6 A
400 V / 4,0 A
24 V / 2 A
230 V / 0,5 A
20 A gL bei 500 V
max. 400 mA
2x 0,5 - 2,5 mm²; 1 x 1,0 - 6,0 mm²
1 level
2 levels
approx. 0.25 kg approx. 0.40 kg
E
2,5 Nm
3 levels
approx. 0.55 kg
2,5 Nm
3 levels
approx. 0.55 kg