Fig. 1.5 RCCB test buttom
Contact arrangement -
ELCB (RCCB)
2-poLE
4-pole
Fig 1.5.a Contact Arrangement
ELCB with circuit breaker
1/2 N
2/1 N
1-pole + N
1/2 3/4
2/1 4/3
2-pole
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
30
Explosion-protected distributions GHG 619
1.5
ELCB (RCCB), 2 and 4-pole; GHG624
"TEST"
Rated voltage:
Pos. 1
Rated current:
Short-circuit protection:
Back-up fuse:
Tripping current:
Component size:
Weight:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
1.5a RCBO with Circuit breaker; GHG625
Rated voltage:
Rated current:
ELCB
Circuit breaker
Aux. contact
Short-circuit protection:
Back-up fuse:
ELCB
Circuit breaker
Tripping current ELCB:
Component size:
Weight:
The technical data relates to standard built-in apparatus.
- If other built-in apparatus is used, the technical data sheets
or the data on the type label shall be observed.
* ELCB with circuit breakers and signal contacts are built into component enclosures in the next size.
1.5.2
Interface Relais R1561
Switching volta
Switching currentge
Braeking capacity
Bild 1.5.2
EATON's Crouse-Hinds Business
Main contact
230/400 V AC up to 240/415 V AC
Aux. contact
up to 230V AC
Main contakt
up to 63A
Aux.contakt
max. 5A
max. 100 A gG
30 mA up to 500 mA
ca.
0,96kg
Main contakt
up to 400 V AC
Aux./Signal contakt
up to 230 V AC
up to 63 A
from 0.5 A up to 32 A (40 A)
max. 5 A
max. 100 A gL
dep. on rated current up to 100 A gL
ca.
0,96kg
min/max
min/max
AC 1 min/max
DC 1 min/max
Contact Arrangement
ELCB with circuit breaker
and Interface Relais R1561
10 kA
2*
3*
4
1,24kg
1,62kg
up to 10 kA depend on circuit breaker
30 mA up to 500 mA
2*
3*
4
1,24kg
1,62kg
12 V / 250 V AC
10 mA / 6A
0,6 VA / 1500 VA (ohmische Last)
0,6 W / 140 W
E