It-230 Interface Pre Installation Configuration; Running The Rs-422 Cable; Hardware Factory Default; Installing The It-230 With Panel - DSC IT-230 RS-422 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

IT-230 INTERFACE PRE INSTALLATION CONFIGURATION

This IT-230 Interface is fixed and shall be installed in the panel by service persons only (service person is defined as
a person having appropriate technical training and experience necessary to be aware of hazards to which that per-
son may be exposed in performing a task and of measures to minimize the risks to that person or other persons).
The IT-230 shall be installed and used within an environment that provides the pollution degree max 2, over voltages
category II, in non-hazardous, indoor locations only. This manual shall be used with the Installation Manual of the
panel which is connected to the IT-230. All instructions specified within the panel manual and the C24-HUB manual
must be observed.
All the local rules imposed by local electrical codes shall be observed and respected during installation.

Running the RS-422 Cable

An RS-422 cable must be connected to the C24-HUB and cable run to the IT-230 module inside the panel.
NOTE: Maximum cable length for RS-422 cable is 305 m (1,000 ft.)
At the C24-HUB, attach wires for RS-422 connection as follows:
1. Securely fasten the TX+ wire on the terminal block.
2. Securely fasten the TX- wire on the terminal block.
3. Connect a 120
, ¼ W resistor between RX+ and RX- terminals on the C24-HUB.
4. Securely fasten the RX+ wire on the terminal block.
5. Securely fasten the RX- wire on the terminal block.
6. Securely fasten the GND wire on the terminal block. (Optional, DSC recommends connection.)
PIN
Signal Name
7. Run the RS-422 Cable from the C24-HUB to the IT-230 mounted inside the panel.

Hardware Factory Default

The IT-230 can be hardware reset to Factory Default by removing AC power, Battery + terminal, and telephone
line, then installing a jumper between the BLK and DEF pins on the IT-230 Keybus connector (left terminal
block) and restarting the IT-230. (See Figure 2.)
NOTE: Installing the Default (DEF) jumper during normal operation has no effect.

Installing IT-230 with PC1616/1832/1864 Panel

WARNING!
B
EFORE INSTALLING THE
POWER
NECT ALL
(a) Insert (5) plastic standoffs
1. To mount the IT-230 in the panel, perform the following:
a. Remove the panel front cover.
b. Remove the 5 white plastic standoffs from the bag provided with the IT-230 kit.
c. Insert the 5 standoffs into the holes on the left side of the panel as shown in Figure 1 (a).
d. Orient the IT-230 with the standoffs on left side of panel and push the IT-230 firmly and evenly onto the
standoffs until it is securely attached to the panel. See Figure 1 (b).
e. Remove the PC-LINK cable from the supplied IT-230 kit and attach one end of the PC-LINK cable to the
PC1616/1832/1864 PC-LINK header (Red wire on Pin 1 of the panel).
f. Attach the other end of the PC-LINK cable to the IT-230 PC-LINK connector. (Black wire on Pin 1).
1
2
TX +
TX -

INSTALLING THE IT-230 WITH PANEL

IT-230
BOARD WITHIN THE
TELEPHONE LINES
AND
Table 3: RS-422 Connector Pin Assignment
3
4
RX +
RX -
A
LARM CONTROLLER ENCLOSURE
.
FROM THE PANEL
(b) Mount IT-230 on standoffs
2
5
GND
,
DISCON
Figure 1: IT-230 Panel Mounting
-

Publicité

Table des Matières
loading

Table des Matières