Configuration using Switches

Adjust the DIP and rotary switches according to the table on the
housing.
Sensor type:
Select the connected sensor type using switches DIP1 to DIP3.
Start value:
Adjust the number (00 ... 99) using the "Start" rotary switches.
Adjust the factor using the switches DIP4, DIP5.
To obtain a falling curve, adjust a start value which is higher than the
end value.
End value:
Adjust the number (00 ... 99) using the "End" rotary switches.
Adjust the factor using the DIP6 switch.
Output signals:
Adjust the output signal using the switches DIP7, DIP8.
Note
After completion of configuration you must cover the
switches with the included self-adhesive polyimide tape.
For information on IrDA interface configuration, please refer
to the instruction manual for the Paraly ® SW 111 software
(accessory).
1.3
2.2
50
Start value (rotary switch)
End value (rotary switch)
DIP S1 (from left to right: 1-8)