Intended Use

The ThermoTrans® P 32100P0/11-S0002-KTA temperature trans mitters
provide connection possibilities all common thermocouples and
resistance thermometers.
When a resistive sensor is connected, 2-, 3-, or 4-wire configuration is
automatically recognized at device startup.
The output signal is adjustable to 0 / 4 ... 20 mA, or 0 ... 5 / 10 V.
The calibrated range selection is performed using DIP and rotary
coding switches. Alternatively, the devices can be configured via
an IrDA interface located in the upper part of the unit. The device
provides a broad-range power supply and galvanic 3-port isolation.
Prior to commissioning and after each change of the configuration,
you must check the intended function of the transmitter (see Safety
Manual, section 5.1 „Functional Checks").

Block diagram

Input
RTD, TC, R
Please note:
When the configuration is changed from 2-wire to 3-wire (or
4-wire) or from 3-wire to 4-wire, this is only recognized after
the device's next restart.
40
Power supply
24 ... 110 V DC
110 ... 230 V AC
Output
0(4) ... 20 mA
0 ... (5)10 V